Permit NumberFIR10-00619
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 805 W FRANKLIN ST
Project NameCRADLEPOINT PLAZA ELEV. UPGRAD
Customer Number 
ePlanReviewNo
Description
This quick permit is to add devices for elevator recall and shunt trip functions. The lobby smoke detectors are to activate recall functions even when the rest of the circuit is in alarm. No general alarm functions shall operate elevator recall functions. No written review comments. No associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/9/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection1/24/20111/25/20111/25/2011APASS
DetailsTroy Cobbley
Permit finaled
Miscellaneous action  1/24/2011 DONE
Research regarding the Elevator fireman's hat light functions: Since 1983, the lobby smoke detectors are required to illuminate the hat light in the elevator (i.e. solid). As of the 2006 NFPA 72, the lobby detectors are still required to illuminate the hat light, but then the elevator machine room smoke detector and elevator shaft smoke detector (if allowed) are to cause a distinct signal (i.e. flashing hat light) to notify the occupants and responding crews of the danger. The elevator in question was installed in 1993, therefore, only the solid light requirement was enforced for lobby smoke detectors. It is recommended that the elevator machine room smoke and the elevator shaft smoke (if there is one) should also illuminate the hat light, but there is not a code requirement for that function prior to 1996.
INSP-Final Inspection1/19/20111/20/20111/20/2011ACANC
DetailsTroy Cobbley
Waiting for letter on elevator recall/firemans hat prior to continueing the inspection.
INSP-Final Inspection1/18/20111/19/20111/19/2011AFAIL
DetailsTroy Cobbley
The only item tested and passed was the smoke detector located in the elevator machine room. The heat detectors did not shunt. The test was stopped at this point. No other items were tested.
Plan assigned to (Stephanie)12/7/2010 12/8/2010 DONE
DetailsStephanie L. Cobbley
Plan assigned to (Stephanie)12/7/2010 12/8/2010 DONE
DetailsStephanie L. Cobbley
1st review completed  12/8/2010 DONE
Alarm Plan Check12/8/2010 12/8/2010 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  12/8/2010 DONE
approved quick permit plans available at front counter
Inspection Record Card- Fire12/8/2010 12/8/2010 DONE
Details
Telephone call  12/8/2010 DONE
t/c w john - permit ready and fees given
Permit Ready to Issue  12/8/2010 DONE
Details
Issue and Print Permit  12/8/2010 DONE
DetailsBarbara Stitt
Application received  12/7/2010