Miscellaneous action | | | 6/15/2011 | | DONE |
|
|
|
Drawings taken to records for scanning.
|
INSP-Final Inspection | 4/11/2011 | 4/12/2011 | 4/12/2011 | A | PASS |
Forrest France
|
|
|
Corrections verified for completion. Acceptance testing passed, fire alarm permit finaled.
|
INSP-Final Inspection | 4/5/2011 | 4/6/2011 | 4/8/2011 | A | PART |
Forrest France
|
|
|
Final pending program changes for accurate solenoid to detector operations at systems 6 and 8. Tampers, low airs, and flows reported okay. New heat detector locations appear acceptable- need to provide appropriate test equipment at next inspection for verification of HD functionality.
|
FIR-Aging Inspection | 3/23/2011 | 3/23/2011 | 3/23/2011 | | PEND |
Forrest France
|
|
|
No call for inspection- Final pending.
|
Issue and Print Permit | | | 12/22/2010 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 12/8/2010 | | 12/20/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 12/20/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 12/20/2010 | | 12/20/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 12/20/2010 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 12/20/2010 | | 12/20/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 12/20/2010 | | DONE |
|
|
|
left vm for john lopez - permit ready and fees given
|
Permit Ready to Issue | | | 12/20/2010 | | DONE |
|
|
|
|
Case Summary | | | 12/8/2010 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 12/8/2010 | | |
|
|
|
|