Permit Information
Permit NumberFIR10-00632
StatusFinaled
Name CRANE ALARM COMPANY
Site Address 199 N 8TH ST
Project NameLUMSDEN RESTAURANT
Customer Number 
ePlanReviewNo
Description
This quick permit is to add a new notification device to an existing fire alarm system to accomodate a tenant improvement. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD10-02415 (FORK - LUMSDEN RESTAURANTS - 1ST STORY - EAST END) The fire sprinkler system substitutes for the 1-hr fire-resistance-rating of the building structure. To remodel an existing 3,756 square foot bar for a new bar/restaurant tenant. Work is to include interior nonbearing walls, a suspended ceiling within the kitchen, a new bar counter, a new grease hood over a new rotisserie oven, millwork (including wood covers for existing floor mounted HVAC units), and finishes. A new exterior ramp accessible to the disabled will be constructed under a separate permit and is required to be completed before occupancy by this tenant. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/9/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection2/7/20112/8/20112/8/2011PPASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Final Inspection2/7/20112/7/20112/7/2011PPASS
DetailsForrest France
Fire alarm permit okay for final.
INSP-Alarm Testing2/3/20112/3/20112/3/2011PPASS
DetailsForrest France
Fire alarm work for the scope of permit passed field test and inspection.
Issue and Print Permit  12/21/2010 DONE
DetailsBarbara Stitt
Plan assigned to (Stephanie)12/13/2010 12/15/2010 DONE
DetailsStephanie L. Cobbley
1st review completed  12/15/2010 DONE
Alarm Plan Check12/15/2010 12/15/2010 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments
PLANS TAKEN FRONT DESK ALARM  12/15/2010 DONE
Approved quick permit plans available at front counter
Telephone call  12/15/2010 DONE
Got a message from Mary F. at ECI letting me know that the candela of the device to the East of the new area is 110cd.
Inspection Record Card- Fire12/15/2010 12/15/2010 DONE
DetailsPatricia Smith
Telephone call  12/15/2010 DONE
t/c w lisa - permit ready and fees given
Permit Ready to Issue  12/15/2010 DONE
Details
Telephone call  12/14/2010 DONE
Left a message for Mary F. at ECI asking to verify the candela of a device to the East of the new area so I can check notification coverage properly.
Application received  12/13/2010