Miscellaneous action | | | 12/16/2011 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 2/23/2011 | 2/24/2011 | 2/24/2011 | P | PASS |
Forrest France
|
|
|
Correction items verified, plan modification resubmital okayed. Final inspection passed.
|
Plan assigned to (Tim) | 2/14/2011 | | 2/23/2011 | | DONE |
Tim Frost
|
|
|
Plan Modification
|
Sprinkler Plan Check | 2/23/2011 | | 2/23/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/23/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 2/23/2011 | | 2/23/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 2/23/2011 | | DONE |
|
|
|
t/c w jim - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 2/23/2011 | | DONE |
|
|
|
|
(F) Reprint permit | | | 2/23/2011 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 2/23/2011 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/22/2011 | | |
Barbara Stitt
|
|
|
|
Sprinkler Plan Check | 2/15/2011 | | 2/15/2011 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 2/15/2011 | | DONE |
Tim Frost
|
|
|
|
Telephone call | | | 2/15/2011 | | DONE |
|
|
|
t/c w jim - permit denied - needs to be picked up and resubmitted
|
Plan resubmittals received | | | 2/14/2011 | | DONE |
Christina Prado
|
|
|
Plan Mod---Received three sets of each--plans FP1, Application, Checklist, United Water letter and sprinkler model information packet. Routed to Tim Frost for review.
|
INSP-Sprinkler Rough-in | 2/7/2011 | 2/8/2011 | 2/8/2011 | A | FAIL |
Forrest France
|
|
|
See plan set for annotations at locations in need of adjustment including coverage at concealed spaces, one area overspaced, matched temp. uprights, one existing head needs replaced, DP at the new freezer not yet installed, plan mod. pending for field changes per contractor.
|
Issue and Print Permit | | | 12/17/2010 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 12/15/2010 | | 12/16/2010 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 12/16/2010 | | 12/16/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/16/2010 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/16/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 12/16/2010 | | 12/16/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 12/16/2010 | | DONE |
|
|
|
t/c w jim darr - permit ready and fees given
|
Permit Ready to Issue | | | 12/16/2010 | | DONE |
|
|
|
|
Application received | | | 12/15/2010 | | |
|
|
|
|