Miscellaneous action | | | 12/16/2011 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 1/21/2011 | 1/21/2011 | 1/21/2011 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 1/11/2011 | 1/11/2011 | 1/12/2011 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Sprinkler Rough-in | 1/2/2011 | 1/3/2011 | 1/3/2011 | A | PASS |
Troy Cobbley
|
|
|
The sprinkler piping located above the ceilings can be covered. See the city approved plans for upright heads at two locations in the warehouse that are located too close to one another.
|
Issue and Print Permit | | | 12/27/2010 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Tim) | 12/15/2010 | | 12/22/2010 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 12/22/2010 | | 12/22/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There ARE annotations on the plans.
|
1st review completed | | | 12/22/2010 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/22/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 12/22/2010 | | 12/22/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 12/22/2010 | | DONE |
|
|
|
left vm for chris - permit ready and fees given
|
Permit Ready to Issue | | | 12/22/2010 | | DONE |
|
|
|
|
Miscellaneous action | | | 12/20/2010 | | DONE |
|
|
|
Sent the following email
Hi John,
I need some info from you.
- Signed copy of Owner's Certificate
-The flow information that was used for the original hydraulic calculation.
- New/current flow test information.
- The vicinity map did not print. Send me one and I will include it in the small documents.
- I need a key plan that shows this area in relationship to the whole building. In the key plan please locate the riser.
- The building permit is listed with having a portion of the occupancy has mercantile. Where is this area.
- How high are they going to store in the warehouse?
- Are there going to be racks? If so what kind?
I may need some more info after I see the owner's certificate. The project will be on hold until this information is recieved.
FYI - Anytime there is a new tenant with a storage area I will need an owners certificate.
Thank you for your time and cooperation.
|
Application received | | | 12/15/2010 | | |
|
|
|
|