Miscellaneous action | | | 6/15/2011 | | DONE |
|
|
|
Drawings taken to records for scanning.
|
INSP-Final Inspection | 4/5/2011 | 4/5/2011 | 4/5/2011 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 4/4/2011 | 4/4/2011 | 4/4/2011 | P | FAIL |
Troy Cobbley
|
|
|
The last remaining hvac unit in the showroom would not turn on so that automatic shutdown could be tested. The other correction items have been addressed.
|
INSP-Final Inspection | 4/1/2011 | 4/1/2011 | 4/1/2011 | P | CANC |
Troy Cobbley
|
|
|
Cancelled due to time constraints.
|
INSP-Final Inspection | 3/31/2011 | 4/1/2011 | 4/1/2011 | A | CANC |
Troy Cobbley
|
|
|
Please call Guy at 6318903 or Bill at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
|
INSP-Final Inspection | 3/23/2011 | 3/24/2011 | 3/24/2011 | A | FAIL |
Forrest France
|
|
|
Final pending correct length sample tube at duct detectors 2 and 3, RTU 1 is not powered at this time, provide cover plate at riser room junction box, label spare FPL at the panel and the riser room, provide locks at the panel circut breaker. Points map and door signage posted while on site. Sprinkler monitoring, FACP, AES and offsite signals okayed.
|
Override - Parcel Holds | 3/23/2011 | 1/1/1900 | 3/23/2011 | | |
|
|
|
fire insp
|
Plan assigned to (Stephanie) | 12/27/2010 | | 12/30/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 12/30/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 12/30/2010 | | 12/30/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved - see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 12/30/2010 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 12/30/2010 | | 12/30/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 12/30/2010 | | DONE |
|
|
|
t/c w lori - permit ready and fees given
|
Permit Ready to Issue | | | 12/30/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/30/2010 | | DONE |
|
|
|
|
Application received | | | 12/27/2010 | | |
|
|
|
|