Permit Information
Permit NumberFIR10-00656
StatusFinaled
Name ALARMCO
Site Address 8727 W FAIRVIEW AVE
Project NameDennis Dillon
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a new fire alarm panel for sprinkler system monitoring and HVAC shutdown/monitoring. An AES RF radio with and IntelliTap is being installed in lieu of the DACT. Permit scope includes a pull station, monitor modules for the dry and wet sprinkler valves, and duct detectors.

Associated building permit: BLD10-01234 Dennis Dillon Nissan - Addition and Remodel - To add onto and remodel two existing building to create a new 30,130 square foot, one story Nissan automobile dealership. The existing 10,365 square foot building, on the northwest corner will be remodeled into a showroom and sales area. The existing 4,860 square foot, pre-manufactured steel building on the south west corner will be converted into a parts storage and sales area. A new 11,815 pre-engineered steel building addition will be constructed on the southeast side of the building for a service area and a 3,045 square foot, wood framed addition will be constructed to tie all of the building together. This area will contain a retail area, parts and service managers’ offices, tire storage, parts storage and part of the parts tech area. This permit also includes related site improvements. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/15/2011 DONE
Drawings taken to records for scanning.
INSP-Final Inspection4/5/20114/5/20114/5/2011PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection4/4/20114/4/20114/4/2011PFAIL
DetailsTroy Cobbley
The last remaining hvac unit in the showroom would not turn on so that automatic shutdown could be tested. The other correction items have been addressed.
INSP-Final Inspection4/1/20114/1/20114/1/2011PCANC
DetailsTroy Cobbley
Cancelled due to time constraints.
INSP-Final Inspection3/31/20114/1/20114/1/2011ACANC
DetailsTroy Cobbley
Please call Guy at 6318903 or Bill at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
INSP-Final Inspection3/23/20113/24/20113/24/2011AFAIL
DetailsForrest France
Final pending correct length sample tube at duct detectors 2 and 3, RTU 1 is not powered at this time, provide cover plate at riser room junction box, label spare FPL at the panel and the riser room, provide locks at the panel circut breaker. Points map and door signage posted while on site. Sprinkler monitoring, FACP, AES and offsite signals okayed.
Override - Parcel Holds3/23/20111/1/19003/23/2011  
fire insp
Plan assigned to (Stephanie)12/27/2010 12/30/2010 DONE
DetailsStephanie L. Cobbley
1st review completed  12/30/2010 DONE
Alarm Plan Check12/30/2010 12/30/2010 PASS
DetailsStephanie L. Cobbley
Plans approved - see review comments
PLANS TAKEN FRONT DESK ALARM  12/30/2010 DONE
Approved plans available at front counter
Inspection Record Card- Fire12/30/2010 12/30/2010 DONE
DetailsPatricia Smith
Telephone call  12/30/2010 DONE
t/c w lori - permit ready and fees given
Permit Ready to Issue  12/30/2010 DONE
Details
Issue and Print Permit  12/30/2010 DONE
Application received  12/27/2010