Miscellaneous action | | | 2/9/2011 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 1/19/2011 | 1/19/2011 | 1/19/2011 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled.
|
INSP-Final Inspection | 1/18/2011 | 1/18/2011 | 1/18/2011 | P | FAIL |
Troy Cobbley
|
|
|
Pull stations tested ok except the new pull station located at the end of the east wing was labeled as "west pull". The new corridor smoke detectors tested ok except the end detector was reported as a trouble signal instead of alarm. The room smoke detectors reported as trouble signals instead of supervisory. Also the room smoke detectors all sounded when a single detector was activated which is incorrect. An additional pull station will be required at the exterior door from the Dining Area. As-builts will need to be provided showing this new pull station and the deletion of a single smoke detector in the middle of the new corridor. No other devices where inspected.
|
Plan resubmittals received | | | 1/14/2011 | | DONE |
Tisha Gallop
|
|
|
received application and three copies of submittal documents and plans; routed to Fire Reveiw.
|
Alarm Plan Check | 1/14/2011 | | 1/14/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
approved - see review comments and redlined plans
|
PLANS TAKEN FRONT DESK ALARM | | | 1/14/2011 | | DONE |
|
|
|
approved redlined plans available at front counter
|
Inspection Record Card- Fire | 1/14/2011 | | 1/14/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 1/14/2011 | | DONE |
|
|
|
t/c w rand - permit ready and fees given
|
Permit Ready to Issue | | | 1/14/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/14/2011 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 12/28/2010 | | 1/14/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 1/12/2011 | | 1/12/2011 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - see review comments.
|
Miscellaneous action | | | 1/12/2011 | | DONE |
|
|
|
Emailed Alarm Star letting them know the plans have been denied and a detailed description for why.
|
Miscellaneous action | | | 1/12/2011 | | DONE |
|
|
|
Denied plans available at front desk.
|
Plan resubmittals received | | | 1/10/2011 | | DONE |
Tisha Gallop
|
|
|
received application and two copies of submittal documents and plans; routed to Fire Review
|
Miscellaneous action | | | 1/6/2011 | | DONE |
|
|
|
denied plans picked up by contractor
|
Telephone call | | | 1/4/2011 | | DONE |
|
|
|
Spoke to Rand Gruber of Alarm Star regarding the pull stations not being shown on the plans submitted. I let him know that per the review comments for the original fire permit (FIR08-00601) pull stations are required at all exits because there are no nurse call stations or other permanent staff locations indicated on the plans with pull stations located per IFC 907.4.1. I let him know that a resubmittal will be required providing those pull stations at existing exits, as well as a pull station is needed at the new exit. He requested that I attache a copy of the original review comments to the redlines of the submittal.
|
1st review completed | | | 1/4/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 1/4/2011 | | 1/4/2011 | | FAIL |
Stephanie L. Cobbley
|
|
|
pull stations are required at all exits. Accurate occupancy types are required to be provided on the permit application. See review comments for further requirements.
|
Miscellaneous action | | | 1/4/2011 | | DONE |
|
|
|
Review comments faxed to vendor indicating a resubmittal is required.
|
Miscellaneous action | | | 1/4/2011 | | DONE |
|
|
|
Denied plans and redlines available at front counter.
|
Miscellaneous action | | | 1/4/2011 | | DONE |
|
|
|
A copy of the fire alarm review comments from FIR08-00601 has been attached to the review comments for this project.
|
Application received | | | 12/28/2010 | | |
|
|
|
|