Miscellaneous action | | | 6/8/2011 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 2/23/2011 | 2/23/2011 | 2/24/2011 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 1/28/2011 | 1/28/2011 | 1/28/2011 | P | PASS |
Tim Frost
|
|
|
Sprinklers were changed to quick response per comment of previous inspection. Corrected minimum spacing issue per previous inspection
|
INSP-Final Inspection | 1/26/2011 | 1/26/2011 | 1/26/2011 | P | CANC |
Forrest France
|
|
|
don Phone #: ###-#### ///don called in and cancelled
|
INSP-Sprinkler Rough-in | 1/12/2011 | 1/12/2011 | 1/13/2011 | P | PART |
Forrest France
|
|
|
Noted three upright heads above the womens restroom ceiling and one ssu at the riser closet yet to be replaced with QR type per scope of work, two uprights at the basement level exceed min. spacing.
|
INSP-Sprinkler Rough-in/Hydro | 1/11/2011 | 1/12/2011 | 1/12/2011 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic testing for the basement and first floor levels completed satisfactory.
|
INSP-Final Inspection | 1/11/2011 | 1/11/2011 | 1/11/2011 | P | PART |
Forrest France
|
|
|
Corrections per last notice at the RDG tenant space verified for completion.
|
INSP-Final Inspection | 1/7/2011 | 1/10/2011 | 1/10/2011 | A | PART |
Forrest France
|
|
|
Partial overhead rough-in completed- see plans for field annotations.
|
INSP-Sprinkler Rough-in | 1/7/2011 | 1/10/2011 | 1/10/2011 | A | PART |
Forrest France
|
|
|
Rough-in inspection for the RDG area as marked on plans with today's date okayed with exceptions including one head at the womens restroom janitor closet yet to be replaced with QR and upright heads at the open office to be in compliance with NFPA 13 8.3.1.3.
|
Plan assigned to (Tim) | 1/4/2011 | | 1/7/2011 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 1/7/2011 | | 1/7/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 1/7/2011 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/7/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 1/7/2011 | | 1/7/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 1/7/2011 | | DONE |
|
|
|
t/c w don - permit ready and fees given
|
Permit Ready to Issue | | | 1/7/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/7/2011 | | DONE |
|
|
|
|
Miscellaneous action | | | 1/5/2011 | | DONE |
|
|
|
Spoke with Don Curtis. I mentioned to him that all sprinklers are required to be quick response type by the building department. He did not have quick response shown on the drawing. Theerfore, he told me to put the project on hold until he remedies the situation.
|
Application received | | | 1/4/2011 | | |
|
|
|
|
Case Summary | | | 1/4/2011 | | DONE |
|
|
|
|