Permit Information
Permit NumberFIR11-00010
StatusFinaled
Name ENTERPRISE ELECTRIC
Site Address 370 N BENJAMIN LN
Project NameAda County Paramedics
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a new manual fire alarm system to include full notification, a pull station, remote annunciator, elevator recall functions, HVAC shutdown/monitoring, and sprinkler system monitoring.
Associated building permit: BLD10-01256 (Ada County Paramedics T.I.) Remodel an existing 15,791sq. ft., 2 story office building proposed for use as Ada County Paramedic office and training facility. Building to be fully sprinklered with a fire alarm system as part of remodel. Sprinkler system is used for allowable area increase and added story for compliance of "A3" occupancy in 2 story building. Addition of 555 sq. ft. 2 story enclosed stair /vestibule / entry and new interior elevator and elevator equipment room. Work includes select demolition at exterior and throughout interior of both floors. Construct new alls to create offices, training rooms, reception, common use and support areas; interior finishes, millwork, electrical, mechanical, plumbing, sprinkler and alarm work, all per reviewed plans. Post maximum occupant load sign of 107, Room 110; 100, Room 11; and 217 when room combined into one room for assembly) drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/15/2011 DONE
Drawings taken to records for scanning.
INSP-Final Inspection4/19/20114/19/20114/19/2011APASS
DetailsTroy Cobbley
Permit finaled.
INSP-Final Inspection4/15/20114/18/20114/18/2011AFAIL
DetailsTroy Cobbley
The elevator service personell did not show up and we were unable to put the system in test. No testing was performed.
INSP-Final Inspection4/14/20114/15/20114/15/2011AFAIL
DetailsTroy Cobbley
Items tested today include the fire sprinkler interconnections, sync of a/v's, connection to the AES panel. Still need to do the elevator, duct detectors and end of line voltage verification, and map at the facp.
Issue and Print Permit  1/24/2011 DONE
DetailsChristina Prado
Plan assigned to (Stephanie)1/6/2011 1/21/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  1/21/2011 DONE
Alarm Plan Check1/21/2011 1/21/2011 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments
PLANS TAKEN FRONT DESK ALARM  1/21/2011 DONE
Approved redlined plans available at front counter
Inspection Record Card- Fire1/21/2011 1/21/2011 DONE
DetailsPatricia Smith
Telephone call  1/21/2011 DONE
t/c w doug - permit ready and fees given
Permit Ready to Issue  1/21/2011 DONE
Details
Application received  1/6/2011