Miscellaneous action | | | 6/8/2011 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 2/9/2011 | 2/10/2011 | 2/10/2011 | A | PASS |
Forrest France
|
|
|
Recieved as-built plans from contractor regarding deleted head at the covered patio per NFPA 13 2007 8.15.7.3(1) exception. C/N items finished, permit finaled.
|
INSP-Final Inspection | 2/9/2011 | 2/10/2011 | 2/9/2011 | A | CANC |
Forrest France
|
|
|
jason Phone #: ###-#### Inspection cancelled from web by: Stan Beus
|
INSP-Final Inspection | 2/4/2011 | 2/7/2011 | 2/7/2011 | A | FAIL |
Forrest France
|
|
|
Missing escutcheons at the new office areas, covered head at one closet, patio at the north side is still missing a sidewall head- provide coverage per plan or document with a plan modification including reason deleted.
|
INSP-Sprinkler Rough-in/Hydro | 1/27/2011 | 1/27/2011 | 1/27/2011 | P | PASS |
Tim Frost
|
|
|
Hydro Passed.
Lower office area not previously inspected was ok to cover.
|
INSP-Sprinkler Rough-in | 1/21/2011 | 1/24/2011 | 1/24/2011 | A | PART |
Forrest France
|
|
|
Overhead okayed for cover at the east side addition sheetrock ceiling. Missing sw head per plan at the covered patio. Remainder of work scope incomplete at this time.
|
Plan assigned to (Tim) | 1/11/2011 | | 1/18/2011 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 1/18/2011 | | 1/18/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/18/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 1/18/2011 | | 1/18/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 1/18/2011 | | DONE |
|
|
|
left message with laura for cameron - permit ready and fees given
|
Permit Ready to Issue | | | 1/18/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/18/2011 | | DONE |
Christina Prado
|
|
|
|
Miscellaneous action | | | 1/14/2011 | | DONE |
Christina Prado
|
|
|
Denied plans given to Shilo Automatic Sprinklers
|
Plan resubmittals received | | | 1/14/2011 | | DONE |
Christina Prado
|
|
|
Received three copies of checklist, application, Re-submittal letter and packet and plans. Ruoted back to Tim for review
|
Sprinkler Plan Check | 1/12/2011 | | 1/12/2011 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 1/12/2011 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 1/12/2011 | | DONE |
|
|
|
Emailed contractor review
|
Telephone call | | | 1/12/2011 | | DONE |
|
|
|
left message w laura for cameron - permit denied - needs to be picked up and resbumitted
|
Application received | | | 1/11/2011 | | |
|
|
|
|