Permit Information
Permit NumberFIR11-00026
StatusFinaled
Name DOHERTY ELECTRIC
Site Address 501 W FRONT ST
Project NameConcordia University Law Schoo
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to extend an existing manual fire alarm system into the addition. The system is to include new remote power supplies (NAC panels), a remote annunciator, a relocated pull station, full notification, HVAC shutdown/monitoring, In-duct detectors for f/s damper shutdown, relocated modules for existing sprinkler system monitoring; alarm, trouble, and supervisory connections to a preaction system panel in the server room (the actuating smoke detectors are connected to the releasing system panel and are not part of the fire alarm system), heat detectors located at Library Office 133 and the double door entry for actuation of a deluge system water curtain, a relay for server room f/s damper shut down upon activation of the preaction system, and relays and detection devices for elevator recall functions.

Associated building permit: BLD10-01853 Concordia University - To construct a 32,565 square foot, three story addition on the west side of an existing 17,565 square foot, two story building. The interior of first floor of the existing building will be entirely demolished, with the exception of the existing accessible restrooms, shower room, mechanical, electrical and copy/fax rooms. The remaining portion of the existing first floor will be remodeled for 6 foot library book stacks, reading areas, small offices, study rooms and library circulation desk and work areas. The existing mezzanine will be expanded to create a 5,310 square foot second floor that will be used primarily for 6 foot book stacks. This second floor area will also contain a small reading area, small conference room, IT Tech area and three small shared study rooms. The first floor of the new addition will contain two large classrooms, a large waiting area, accessible restrooms, two small study rooms, and four storage areas for various types of storage. The second floor of the new addition will contain four classrooms of varying sizes, a student lounge, a faculty lounge, two accessible restrooms, a chapel, four small conference rooms, a mechanical room and four storage rooms. The third floor of the new addition contains primarily administrative and faculty offices, with one classroom, two large accessible restrooms and unisex accessible restroom. This floor also contains a mechanical room and janitor closet. The foundation was constructed under building permit BLD10-01393. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/13/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection10/3/201110/4/201110/4/2011PPASS
DetailsForrest France
Noted corrections verified for completion. Fire alarm permit finaled.
INSP-Final Inspection9/29/20119/30/20119/30/2011AFAIL
DetailsForrest France
The auxiliary power supply arrangement for the IPDACT does not meet product installation guidelines. Wiring must be in accordance with NFPA 70 and 72. Address correction for account monitoring completed while on site.
INSP-Final Inspection8/18/20118/19/20118/19/2011APART
DetailsForrest France
Completed remainder of acceptance testing for the new system. Final pending installation and testing of the new IP-DACT per approved plan.
INSP-Final Inspection8/17/20118/18/20118/18/2011APART
DetailsForrest France
Completed testing for ID and DD at the 1st, 2nd, 3rd floor and roof. Noted address changes at two ID on the first floor and the two RTU's AC1 and AC2. IP-DACT per plan has not been installed- phone lines have been provided interm.
INSP-Final Inspection8/16/20118/17/20118/17/2011PNR
DetailsForrest France
Signals not recieved at central station monitoring. Walkthrough notification testing for the 1st, 2nd and 3rd floors completed acceptable.
Inspection Record Card- Fire8/16/2011 8/16/2011 DONE
DetailsPatricia Smith
Permit Ready to Issue  8/16/2011 DONE
Details
Telephone call  8/16/2011 DONE
t/c w morgan - permit (plan mod) ready and fees given
CHANGE STATUS TO (ISS)  8/16/2011 DONE
DetailsTisha Gallop
picked up approved plan mod
Alarm Plan Check8/15/2011 8/15/2011 PASS
DetailsStephanie L. Cobbley
Plan modification approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  8/15/2011 DONE
Approved redlined plan modification documents available at front counter.
Plan assigned to (Stephanie)8/11/2011 8/15/2011 DONE
DetailsStephanie L. Cobbley
Plan Mod
Plan resubmittals received  8/11/2011  
Plan Modification
INSP-Final Inspection8/8/20118/9/20118/9/2011AFAIL
DetailsForrest France
Noted items during initial walkthrough include 1st floor- provide WP notification devices at shower 140 and unisex 117, notification at study rooms 119A and 119B are overspaced, noted two added ID at store room 115 not shown on plans. 2nd floor- provide signage at the FACP room, install a SD at the panel room, TS, PS and FS at the preaction riser are not shown on plans, hall 212A and 212B notification devices are overspaced/obstructed, IT tech room A/V is overspaced. 3rd floor- casual seating area lacks visual coverage, hall 345 is overspaced. Provide record of inspection and testing including a list of signals per fire code review notes. See also items # 2,3, 7, and 33 on review comments. Post accurate map at the panel. Field modifications including two additional ID, 14 relay modules for AHU shutdown, 4 fire sprinkler monitor modules, and 3 DH to be shown on resubmital plans and matrix as discussed.
INSP-Conference7/13/20117/13/20117/14/2011PDONE
DetailsForrest France
Regarding requirements per IMC 2009 section 606 smoke detection systems control.
Alarm Plan Check6/8/2011 6/8/2011 PASS
DetailsStephanie L. Cobbley
Approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  6/8/2011 DONE
Approved redlined plans available at front counter.
Permit Ready to Issue  6/8/2011 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire6/8/2011 6/8/2011 DONE
DetailsBarbara Stitt
Telephone call  6/8/2011 DONE
DetailsBarbara Stitt
Left a message for Mike with Doherty Electric that permit is ready & fees due on 6-8-11 @ 12:20pm//BAS
Issue and Print Permit  6/8/2011 DONE
Plan assigned to (Stephanie)1/18/2011 6/8/2011 DONE
DetailsStephanie L. Cobbley
Plan resubmittals received  6/1/2011  
DetailsBarbara Stitt
1st review completed  2/7/2011 DONE
Alarm Plan Check2/7/2011 2/7/2011 FAIL
DetailsStephanie L. Cobbley
Plans denied. Please see redlines and review comments.
Telephone call  2/7/2011 DONE
Called to let Rob Ahten know that I would need to either deny the plans (thus one review fee), or I could approve them with the understanding a plan modification would be required (additional review fee). He opted to have me deny the plans. I let him know he could come pick them up and that I would fax him the review comments.
Miscellaneous action  2/7/2011 DONE
Faxed review comments to contractor.
Miscellaneous action  2/7/2011 DONE
DetailsTisha Gallop
picked up denied plans
Telephone call  1/26/2011 DONE
Contractor asked to switch review 'spots' with Fir10-00415 due to urgency. This submittal will be reviewed as if it were submitted on Jan. 24th.
Application received  1/18/2011