Miscellaneous action | | | 9/6/2011 | | DONE |
|
|
|
Taken to records for scanning.
|
INSP-Final Inspection | 8/8/2011 | 8/9/2011 | 8/9/2011 | A | PASS |
Forrest France
|
|
|
Reinspection for noted correction items passed. Fire alarm permit finaled.
|
INSP-Final Inspection | 8/5/2011 | 8/8/2011 | 8/8/2011 | A | PART |
Forrest France
|
|
|
Correction items include; provide accurate descriptors for initiating devices at the north portable, two H/S at the first floor are not functional, missing FS cover at the sprinkler riser, add PIV descriptor. Remainder of previous c/n items verified for completion.
|
INSP-Final Inspection | 8/4/2011 | 8/5/2011 | 8/5/2011 | A | FAIL |
Troy Cobbley
|
|
|
No inspection was performed due to signal reports not being provided as required per the fire alarm plan review general comments. A correction notice was left with Jerry, the job site superintendant.
|
INSP-Final Inspection | 8/3/2011 | 8/4/2011 | 8/4/2011 | P | FAIL |
Troy Cobbley
|
|
|
Started the fire alarm testing by verifying the fire sprinkler interconnections. When we called the monitoring company I found that no supervisory signals had been received. It appears that account is not set up for these. No further testing was done. Separate phone lines have been verified. Forrest's redline comments have not been verified.
|
INSP-Final Inspection | 7/28/2011 | 8/1/2011 | 8/1/2011 | A | FAIL |
Forrest France
|
|
|
See stamped plans for red-lined annotations at the basement, first and second floors regarding noted corrections and adjustments to be made prior to final.
|
INSP-Alarm Testing | 7/28/2011 | 8/1/2011 | 7/28/2011 | A | CANC |
Forrest France
|
|
|
Please call Ken with time of test. ###-#### Phone #: ###-#### >> Inspection requested via web by Jason Minnick Inspection cancelled from web by: Jason Minnick
|
Issue and Print Permit | | | 3/24/2011 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 1/20/2011 | | 3/23/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan assigned to (Stephanie) | 3/16/2011 | | 3/23/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 3/23/2011 | | 3/23/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Resubmittal approved - see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 3/23/2011 | | DONE |
|
|
|
Approved resubmittal documents available at front counter.
|
Inspection Record Card- Fire | 3/23/2011 | | 3/23/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 3/23/2011 | | DONE |
|
|
|
t/c w lisa - permit ready and fees given
|
Permit Ready to Issue | | | 3/23/2011 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/16/2011 | | DONE |
Christina Prado
|
|
|
Received two copies of checklist; two copies of application; two copies of fire alarm system packets; and two sets of plans E3.1, E0.1S, E1.1S, E2.1S, FA-1 & FA-2. Routed to Stephanie for review
|
Miscellaneous action | | | 2/4/2011 | | DONE |
|
|
|
picked up denied plans.
|
1st review completed | | | 2/3/2011 | | DONE |
|
|
|
|
Telephone call | | | 2/3/2011 | | DONE |
|
|
|
Spoke to Jason to let him know there are several areas that have inadequate visual coverage. I let him know that I could either reject the plans and he could resubmit, thus paying one review fee; or I could go ahead and approve them, but that a plan modification would be required. I let him know that the plan modification would be an additional review fee. He opted to have me reject the plans.
|
Alarm Plan Check | 2/3/2011 | | 2/3/2011 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - see review comments and redlined plans.
|
Miscellaneous action | | | 2/3/2011 | | DONE |
|
|
|
Denied plans available for customer pick-up
|
Miscellaneous action | | | 2/3/2011 | | DONE |
|
|
|
Faxed review comments to contractor.
|
Application received | | | 1/20/2011 | | |
|
|
|
|