Miscellaneous action | | | 6/15/2011 | | DONE |
|
|
|
Drawings taken to records for scanning.
|
INSP-Final Inspection | 2/17/2011 | 2/18/2011 | 2/18/2011 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 2/16/2011 | 2/17/2011 | 2/17/2011 | A | FAIL |
Troy Cobbley
|
|
|
All signals except loss of A/C were reported to the central station. One tamper switch is reporting as a trouble instead of a supervisory.
|
Plan assigned to (Stephanie) | 2/8/2011 | | 2/16/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 2/16/2011 | | 2/16/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
1st review completed | | | 2/16/2011 | | DONE |
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 2/16/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Inspection Record Card- Fire | 2/16/2011 | | 2/16/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 2/16/2011 | | DONE |
|
|
|
t/c w kenny - permit ready and fees given
|
Permit Ready to Issue | | | 2/16/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/16/2011 | | DONE |
|
|
|
|
Application received | | | 2/8/2011 | | |
|
|
|
|