Permit NumberFIR11-00060
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3883 N GARDEN CENTER WAY
Project NameLive/Work Unit #29
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of providing a 13D sprinkler system for a live/work unit. Extended coverage residential sprinklers were utilized with vary spacing (please see hydraulic summary for details).


Building Department Scope:

(live/work unit 29) ***PLAN MODIFICATION ON 1/10/2011 - TO MODIFY THE INTERIOR PORTION OF THE SECOND STORY DWELLING UNIT PER THE APPROVED FLOOR PLAN. SRZ***PLAN MODIFICATION ON 12-23-2010 - TO MODIFIY THE INTERIOR PORTION OF THE 2ND STORY DWELLING UNIT. WORK TO INCLUDE: ROTATE THE ORIGINAL LAYOUT OF THE KITCHEN/BATHROOM DESIGN CREATING A LARGER MASTER SUITE, REDUCING THE KITCHEN AREA, AND PROVIDING A LARGER LIVING SPACE PER THE APPROVED PLANS. SRZ***To construct a 1850 sq.ft., two story, Live/Work unit (Townhouse) on a zero lot line. The First story includes a 713 sq.ft. non-residential use, operated by the tenant and shall comply with section 419 of the 2007 International Building Code Supplement. The first story also has a 51 sq.ft. covered porch, a 27 sq.ft. covered patio, and a 464 sq.ft. attached two car garage. A maximum of five non-residential workers or employees are allowed to occupy the non-residential area at any one time. The second story includes a 1137 sq.ft., two bedroom, two bathroom, dwelling unit with a 89 sq.ft. balcony. The dwelling unit shall comply with the 2006 International Residential Code for a Single family townhouse dwelling. This building shall conform to section 903.3.1.3 of the 2006 IBC. An automatic sprinkler system shall be installed throughout in accordance with NFPA 13D. Any and all NFPA 13D systems shall be equipped with an alarm initiating device commonly referred to as a flow switch, and an outside alarm indicating device. A Fire Sprinkler Permit is required prior to beginning any fire sprinkler work. "This lot is within a Floodplain area. An elevation certificate is required to be submitted to and approved by Jim Wyllie, Public Works Department, prior to calling for a framing inspection." All work per the approved plans, engineering, plan review report, and alternate agreements on file. DRH07-00466, DRH08-00126, and CUP07-00121 per Planning and Zoning. **SRZ**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/8/2011 DONE
Sent to records for scanning.
INSP-Final Inspection4/14/20114/15/20114/15/2011APASS
DetailsTroy Cobbley
permit finaled
INSP-Supply line flush4/14/20114/14/20114/14/2011PPASS
DetailsTroy Cobbley
Supply line flush and the testing of the flow switch passed.
INSP-Final Inspection4/12/20114/13/20114/13/2011PFAIL
DetailsTroy Cobbley
provide head wrench, provide signage, provide underground flush, test flow switch
INSP-Sprinkler Rough-in3/7/20113/8/20113/8/2011APASS
DetailsForrest France
Noted correction items per inspection dated 3/3/11 verified for completion. Overhead work okay to cover.
INSP-Sprinkler Rough-in3/2/20113/3/20113/3/2011PFAIL
DetailsTroy Cobbley
See the approved as-builts for items that need corrected. Revised as-builts will be required.
CHANGE STATUS TO (ISS)  3/2/2011 DONE
DetailsChristina Prado
Per tim Frost
Plan resubmittals received  2/25/2011 DONE
DetailsChristina Prado
PLAN MOD** Received four copies of Plan Mod letter; application; checklist and plan FP1. Routed to Tim Frost for review.
Issue and Print Permit  2/16/2011 DONE
Plan assigned to (Tim)2/9/2011 2/15/2011 DONE
DetailsTim Frost
Sprinkler Plan Check2/15/2011 2/15/2011 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  2/15/2011 DONE
DetailsTim Frost
Inspection Record Card- Fire2/15/2011 2/15/2011 DONE
DetailsPatricia Smith
Telephone call  2/15/2011 DONE
t/c w cameron - permit ready and fees given
Permit Ready to Issue  2/15/2011 DONE
Details
Plan resubmittals received  2/14/2011 DONE
DetailsChristina Prado
Received three copies of application, checklist, correction letter and notes, Fire Plan submittals and plans FP1. Routed to Tim Frost for review.
Sprinkler Plan Check2/11/2011 2/11/2011 FAIL
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  2/11/2011 DONE
DetailsTim Frost
Telephone call  2/11/2011 DONE
left vm for cameron - permit denied - needs to be picked up and resubmitted
Application received  2/9/2011  
Pending Assignment by SAM2/9/2011 2/9/2011 DONE
DetailsTisha Gallop