Miscellaneous action | | | 6/15/2011 | | DONE |
|
|
|
Drawings taken to records for scanning.
|
INSP-Final Inspection | 6/1/2011 | 6/1/2011 | 6/1/2011 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 5/31/2011 | 5/31/2011 | 5/31/2011 | P | FAIL |
Forrest France
|
|
|
Zones, points and descriptors at offsite monitoring do not accurately correlate with signals transmitted- example; zone 36 point 11 duct detector supervisory reported as zone 11 manual pull station trouble.
|
INSP-Final Inspection | 5/27/2011 | 5/27/2011 | 5/27/2011 | P | FAIL |
Troy Cobbley
|
|
|
Need updated map at the facp showing the correct duct smoke detector addresses and the new pull station at the west exit door. Also the duct detector addresses tested do not correspond with the addresses received at central. To final a map and reverification of duct detector addresses will be required.
|
INSP-Final Inspection | 5/26/2011 | 5/27/2011 | 5/27/2011 | A | PART |
Troy Cobbley
|
|
|
Four strobes are over spaced. One strobe needs to be lowered since it is obstructed by duct work. The central station did not receive all of the alarm signals. The inspection had to be stopped due to time constraints. The remaining inspection is scheduled for later today.
|
INSP-Final Inspection | 5/25/2011 | 5/26/2011 | 5/26/2011 | A | CANC |
Troy Cobbley
|
|
|
Cancelled per Tom due to a ground fault on one of the existing circuits. To be rescheduled.
|
Plan assigned to (Stephanie) | 3/10/2011 | | 3/23/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 3/23/2011 | | 3/23/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 3/23/2011 | | DONE |
|
|
|
Approved plan modifications available at front desk.
|
Inspection Record Card- Fire | 3/23/2011 | | 3/23/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 3/23/2011 | | DONE |
|
|
|
t/c w tom - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 3/23/2011 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 3/23/2011 | | DONE |
Christina Prado
|
|
|
|
Plan resubmittals received | | | 3/10/2011 | | DONE |
Christina Prado
|
|
|
PLAN MOD*** Received one copy of application and checklist; two copies of Fire Alarm Data Sheets; and two copies of plans FA-0.0, FA-1.0, FA-2.0, and FA-2.1. Routed to Stephanie for review
|
Issue and Print Permit | | | 3/1/2011 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (Stephanie) | 2/11/2011 | | 2/14/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan assigned to (Stephanie) | 2/11/2011 | | 2/14/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 2/14/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 2/14/2011 | | 2/14/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit approved - no written review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 2/14/2011 | | DONE |
|
|
|
Approved quick permit documents available at front counter.
|
Inspection Record Card- Fire | 2/14/2011 | | 2/14/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 2/14/2011 | | DONE |
|
|
|
t/c w tom - permit ready and fees given
|
Permit Ready to Issue | | | 2/14/2011 | | DONE |
|
|
|
|
Application received | | | 2/11/2011 | | |
|
|
|
|