Permit Information
Permit NumberFIR11-00087
StatusFinaled
Name KOYAMA ELECTRIC
Site Address 3041 W PASADENA DR
Project NameMWI Veterinary Supply
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to add corridor smoke detection for fire/smoke damper control and notification to the existing Fire Alarm system to accommodate a tenant improvement.
Associated building permit: BLD10-02939 (MWI VETERINARY SUPPLY - ENTIRE BUILDING) Fire sprinklers used to substitute for the 1-hr fire-resistance-rating of the building. To remodel an existing building (basement, 1st story, 2nd story, and 3rd story) for a new office tenant. Each story has a floor area of about 15,000 square feet. Work is to include interior nonbearing walls, new or relocated doors, millwork, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. The fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/15/2011 DONE
Drawings taken to records for scanning.
INSP-Final Inspection4/4/20114/5/20114/5/2011PPASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Final Inspection3/31/20114/1/20114/1/2011PPART
DetailsForrest France
Reinspection items passed. Final pending repair of one damper motor at the 3rd floor.
INSP-Alarm Testing3/30/20113/30/20113/30/2011PPART
DetailsForrest France
Final pending noted corrections.
INSP-Final Inspection3/25/20113/29/20113/29/2011PPART
DetailsForrest France
Fire alarm testing completed. Items needed for final include powered dampers at the third floor to verify operation, repair existing notification device at the 2nd floor comm. room, relocate MPat the main entry vestibule 1st floor, replace/add horns at the basement mechanical room, provide signage at the door to the FACP room per review note #21.
INSP-Conference3/18/20113/18/20113/18/2011PDONE
DetailsForrest France
On site meeting with general contractor regarding fire alarm work in progress, review notes, red-line comments, appliance locations, testing schedule, code requirements, etc.
Plan assigned to (Stephanie)2/23/2011 3/4/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  3/4/2011 DONE
Alarm Plan Check3/4/2011 3/4/2011 PASS
DetailsStephanie L. Cobbley
Approved with redlines and review comments
PLANS TAKEN FRONT DESK ALARM  3/4/2011 DONE
Approved redlined plans available at front counter.
Inspection Record Card- Fire3/4/2011 3/4/2011 DONE
DetailsPatricia Smith
Telephone call  3/4/2011 DONE
t/c w john - permit ready and fees given
Permit Ready to Issue  3/4/2011 DONE
Details
Issue and Print Permit  3/4/2011 DONE
DetailsTisha Gallop
Application received  2/23/2011