Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberFIR11-00093
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 11311 W CHINDEN BLVD
Project NameHP BLDG 4 ELEV. DAMPER CONTRL
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide two control ZAMs and tie them in to the existing fire alarm system. One ZAM is to open a damper upon activation of the elevator shaft smoke detector. The other is to program the elevator fireman's hat light to blink. There are no written review comments. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  1/20/2012 DONE
Plans taken to records for scanning.
INSP-Final Inspection11/17/201111/17/201111/17/2011PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing11/17/201111/17/201111/17/2011PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro11/17/201111/17/201111/17/2011PCANC
DetailsTroy Cobbley
Call for access Phone #: 208941146 >> Inspection requested via mobile web by Brian Anderson Inspection cancelled via moblie web on Thursday, November 17, 2011.
Issue and Print Permit  3/3/2011 DONE
DetailsBarbara Stitt
Plan assigned to (Stephanie)2/28/2011 3/2/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  3/2/2011 DONE
Alarm Plan Check3/2/2011 3/2/2011 FAIL
DetailsStephanie L. Cobbley
Quick permit denied. Appropriate functions for the elevator and the smoke at the top of the shaft were not provided.
Miscellaneous action  3/2/2011 DONE
Denied plans available at the front counter
Miscellaneous action  3/2/2011 DONE
A sheet was faxed to the contractor explaining the reason for the permit rejection.
Plan resubmittals received  3/2/2011 DONE
received 1 resubmittal (Quick Permit) sent to SLC
Alarm Plan Check3/2/2011 3/2/2011 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  3/2/2011 DONE
Approved quick permit plans available at front counter.
Inspection Record Card- Fire3/2/2011 3/2/2011 DONE
DetailsBarbara Stitt
Permit Ready to Issue  3/2/2011 DONE
DetailsBarbara Stitt
Telephone call  3/2/2011 DONE
DetailsBarbara Stitt
Called and left a voice message for Charlie Bayne that permit is ready & fees due on 3-2-11 @ 2:50 pm//BAS
Telephone call  2/28/2011 DONE
Spoke to Charlie at SimplexGrinnell regarding an incomplete operations matrix. I asked him to please verify all of the functions this particular device is to perform and revise the matrix accordingly. I let him know he could just email me a new matrix if that is more convenient.
Application received  2/28/2011