Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR11-00098
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 501 W FRONT ST
Project NameConcordia University Law Schoo
Customer NumberCLEAN AGENT
ePlanReviewNo
Description
The Fire Protection Scope of work consists of a HFC-125 clean agent system to protect a computer server room. One 180º nozzle is being utilized with two smoke detectors.


Building Department Scope:

Concordia University - To construct a 32,565 square foot, three story addition on the west side of an existing 17,565 square foot, two story building. The interior of first floor of the existing building will be entirely demolished, with the exception of the existing accessible restrooms, shower room, mechanical, electrical and copy/fax rooms. The remaining portion of the existing first floor will be remodeled for 6 foot library book stacks, reading areas, small offices, study rooms and library circulation desk and work areas. The existing mezzanine will be expanded to create a 5,310 square foot second floor that will be used primarily for 6 foot book stacks. This second floor area will also contain a small reading area, small conference room, IT Tech area and three small shared study rooms. The first floor of the new addition will contain two large classrooms, a large waiting area, accessible restrooms, two small study rooms, and four storage areas for various types of storage. The second floor of the new addition will contain four classrooms of varing sizes, a student lounge, a faculty lounge, two accessible restrooms, a chapel, four small conference rooms, a mechanical room and four storage rooms. The third floor of the new addition contains primarily administrative and faculty offices, with one classroom, two large accessible restrooms and unisex accessible restroom. This floor also contains a mechanical room and janitor closet. The foundation was constructed under building permit BLD10-01393. All construction per the approved plans and attached comment list. JCM

Fire Sprinkler System Design/Spacing:

The room is designed for a minimum concentration of 8.25% at 70ºF in a room of 2120.88 Ft³ in 9.29 seconds utilizing 56# of agent from a 100# cylinder.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/22/2011 DONE
Sent to records for scanning.
INSP-Final Inspection8/19/20118/22/20118/22/2011PPASS
DetailsForrest France
Site testing and inspection completed acceptable. Permit finaled.
INSP-Final Inspection8/19/20118/19/20118/19/2011PCANC
DetailsForrest France
Overbooked
Case Summary  8/17/2011  
Issue and Print Permit  3/29/2011 DONE
DetailsBarbara Stitt
Sprinkler Plan Check3/28/2011 3/28/2011 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  3/28/2011 DONE
DetailsTim Frost
Permit Ready to Issue  3/28/2011 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire3/28/2011 3/28/2011 DONE
DetailsBarbara Stitt
Telephone call  3/28/2011 DONE
DetailsBarbara Stitt
Left message for Ken Roule that permit is ready & fees due on 3-28-11 @ 9:15am
Plan resubmittals received  3/25/2011 DONE
DetailsTisha Gallop
received application, and three copies of submittal folder and plans; taken to Fire Review.
Plan assigned to (Tim)3/4/2011 3/22/2011 DONE
DetailsTim Frost
Pending Assignment by SAM3/3/2011 3/4/2011 DONE
DetailsPatricia Smith
Sprinkler Plan Check3/4/2011 3/4/2011 FAIL
DetailsTim Frost
Please, see attached comments.
There are annotations on the plans.
1st review completed  3/4/2011 DONE
DetailsTim Frost
Miscellaneous action  3/4/2011 DONE
Emailed review to contractor.
Telephone call  3/4/2011 DONE
t/c w ken - permit denied - needs to be picked up and resubmitted
Application received  3/3/2011