INSP-Final Inspection | 4/18/2011 | 4/19/2011 | 4/20/2011 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 4/14/2011 | 4/15/2011 | 4/15/2011 | A | FAIL |
Forrest France
|
|
|
Noted overspaced coverage at the design room adjacent to the new sheetrock partition wall at the roof deck to patio access storefront.
|
INSP-Sprinkler Rough-in | 3/16/2011 | 3/17/2011 | 3/17/2011 | A | PASS |
Troy Cobbley
|
|
|
Sprinkler piping is ok to cover
|
Plan assigned to (Tim) | 3/4/2011 | | 3/14/2011 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 3/14/2011 | | 3/14/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 3/14/2011 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/14/2011 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 3/14/2011 | | DONE |
|
|
|
Received addtional information, owner's certificate, new flow test.
|
Inspection Record Card- Fire | 3/14/2011 | | 3/14/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 3/14/2011 | | DONE |
|
|
|
t/c w brodie - permit ready and fees given
|
Permit Ready to Issue | | | 3/14/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/14/2011 | | DONE |
|
|
|
|
Miscellaneous action | | | 3/7/2011 | | DONE |
|
|
|
RFI
I need an owner's certificate that accurately reflects the commodity (I am assuming paper files in cardboard boxes, Class III), type of storage, height, packaging, aisle widths, etc.
I need the original flow test information and new flow test information. Hydraulic calculation may very well be required on this project. It appears you are adding two sprinklers to the each branch line. I cannot be sure because the drawing is so small but it looks like you are in the hydraulic most remote area. Please, verify and let me know.
I will let you know if a full size resubmittal is required once I have received the above information.
Thank you for your time and cooperation.
|
Application received | | | 3/4/2011 | | |
|
|
|
|
Pending Assignment by SAM | 3/4/2011 | | 3/4/2011 | | DONE |
Patricia Smith
|
|
|
|