Permit Information
Permit NumberFIR11-00116
StatusFinaled
Name M2 AUTOMATION
Site Address 715 S CAPITOL BLVD
Project NameBOISE LIBRARY
Customer Number 
ePlanReviewNo
Description
This quick permit is to add a strobe only to a new lactation room. The strobe will be tied in to existing NAC 4B-2 on the existing 5499 intelligent power module. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD10-02879 (BOISE LIBRARY LACTATION ROOM) Permit is to add a lactation room to an existing library. Approval contingent upon adhering to the approved plans on file. Work to include: construction of interior non-bearing walls to create the new lactation room, installation of new accessible door / hardware, installation of new exhaust fan, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. This building is sprinklered for 1-hr. substitution. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/15/2011 DONE
Drawings taken to records for scanning.
INSP-Final Inspection3/18/20113/21/20113/21/2011APASS
DetailsForrest France
Scope of work completed, fire alarm testing passed. Permit finaled.
Plan assigned to (Stephanie)3/16/2011 3/18/2011 DONE
DetailsStephanie L. Cobbley
Plan assigned to (Stephanie)3/16/2011 3/18/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  3/18/2011 DONE
Telephone call  3/18/2011 DONE
Called Neal Timmerman to request a new floorplan. The one faxed over has very faint lines for the layout of the scope of work. I requested a new one that had a better representation of the floorplan layout. He said it would be later this afternoon but that he would get it for me.
Miscellaneous action  3/18/2011 DONE
Received requested information
Alarm Plan Check3/18/2011 3/18/2011 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  3/18/2011 DONE
Approved quick permit plans available at front counter.
Inspection Record Card- Fire3/18/2011 3/18/2011 DONE
DetailsPatricia Smith
Permit Ready to Issue  3/18/2011 DONE
Details
Issue and Print Permit  3/18/2011 DONE
Telephone call  3/18/2011 DONE
left m for neal - permit ready and fees given
Application received  3/16/2011