Miscellaneous action | | | 6/15/2011 | | DONE |
|
|
|
Drawings taken to records for scanning.
|
INSP-Final Inspection | 4/21/2011 | 4/22/2011 | 4/22/2011 | A | PASS |
Forrest France
|
|
|
Correction items per last inspection verified for completion. Fire alarm permit finaled.
|
INSP-Final Inspection | 4/21/2011 | 4/21/2011 | 4/21/2011 | P | FAIL |
Troy Cobbley
|
|
|
All items tested ok but the signals sent out report a general fire and supervisory signals for both the 358 and 370 addresses. The signal has to be specific for the address. Signals need to be resent from both buildings to verify corrections. The duct smoke detector was missing the sample tube and was installed while I waited. The tamper switch on the PIV was installed backwards and wired backwards and was also repaired while I waited.
|
INSP-Final Inspection | 4/20/2011 | 4/21/2011 | 4/21/2011 | A | FAIL |
Troy Cobbley
|
|
|
Installation does not match plans. The modules that were to be removed are still installed. Also the the wire between the two buildings is supposed to meet requirements in NEC article 800 and it does not. No testing was performed.
|
Plan assigned to (Stephanie) | 4/8/2011 | | 4/20/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 4/20/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 4/20/2011 | | 4/20/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 4/20/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Inspection Record Card- Fire | 4/20/2011 | | 4/20/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 4/20/2011 | | DONE |
|
|
|
customer in lobby
|
Permit Ready to Issue | | | 4/20/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/20/2011 | | DONE |
|
|
|
|
Telephone call | | | 4/19/2011 | | DONE |
|
|
|
Spoke to Rob Ahten and requested a data sheet for the transient/lightning protection modules. He stated he would not be able to get it to me until tomorrow morning.
|
Telephone call | | | 4/19/2011 | | DONE |
|
|
|
Called Rob Ahten to let him know the part number he provided for the transient/lightning protection module is not listed for use with the Silent Knight Fire Alarm Panel and that he would need to get with the vendor to obtain the correct part/data sheet. In addition, I let him know he would also need to provide the transient/surge protection for the remote annunciator panel.
|
Application received | | | 4/8/2011 | | |
|
|
|
|