Miscellaneous action | | | 9/22/2011 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 6/28/2011 | 6/29/2011 | 6/29/2011 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit work passed final walkthrough.
|
INSP-Final Inspection | 6/28/2011 | 6/28/2011 | 6/28/2011 | P | PART |
Forrest France
|
|
|
please call Don. Phone #: ###-#### >> Inspection requested via web by Jeff Packham
|
INSP-Sprinkler Rough-in | 5/25/2011 | 5/26/2011 | 5/26/2011 | A | CANC |
Forrest France
|
|
|
See stamped plans for overhead work at grid ceilings okayed for cover marked with today's date.
|
INSP-Sprinkler Rough-in | 4/21/2011 | 4/21/2011 | 4/21/2011 | A | PART |
Forrest France
|
|
|
Rough-in at the first floor only per annotations okay to cover.
|
INSP-Sprinkler Rough-in | 4/19/2011 | 4/20/2011 | 4/20/2011 | A | PART |
Forrest France
|
|
|
Okay to cover overhead work above areas with sheetrock ceilings as marked and clouded on approved plans. Non-sprinklered concealed spaces at three locations enclosed by combustible construction to be filled with insulation to meet exceptions allowed per NFPA 13.
|
Sprinkler Plan Check | 4/19/2011 | | 4/19/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/19/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 4/19/2011 | | 4/19/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 4/19/2011 | | DONE |
|
|
|
t/c w brodie - permit ready and fees given
|
Permit Ready to Issue | | | 4/19/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/19/2011 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Tim) | 4/12/2011 | | 4/19/2011 | | DONE |
Tim Frost
|
|
|
|
Plan resubmittals received | | | 4/18/2011 | | DONE |
Christina Prado
|
|
|
Received three copies of application, checklist, hydralic calcs for 1, hydralic calcs for 1 additional, and plans FP1 of 1. Routed to Tim Frost for review
|
Sprinkler Plan Check | 4/15/2011 | | 4/15/2011 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
Miscellaneous action | | | 4/15/2011 | | DONE |
|
|
|
Emailed review to contractor
|
Telephone call | | | 4/15/2011 | | DONE |
|
|
|
left message for jim - permit denied, needs to be picked up and resubmitted
|
Sprinkler Plan Check | 4/14/2011 | | 4/14/2011 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 4/14/2011 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 4/14/2011 | | DONE |
|
|
|
Emailed review to contractor.
|
Telephone call | | | 4/14/2011 | | DONE |
|
|
|
left message for jim - permit denied, needs to be picked up and resubmitted
|
Plan resubmittals received | | | 4/14/2011 | | DONE |
|
|
|
received 1 letter of transmittal,1 response,3 sets of plans and 3 applications sent to fire ///dld
|
Application received | | | 4/12/2011 | | |
|
|
|
|