Permit Information
Permit NumberFIR11-00176
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 3614 W STATE
Project NameAlbertson's #189
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to install two new NAC panels and new notification devices due to a tenant remodel.

Associated building permit: BLD10-02790 (ALBERTSON’S – Store # 189) Permit is to remodel an existing 57,015 square foot supermarket (Originally permitted under BLD98-02505). Approval contingent upon adhering to the approved plans on file and attached structural calcs. Work to include: construction of new customer service counters at the existing pharmacy, installation of new suspended walls at dairy cooler, placement of new roof top equipment, add new plumbing (floor drains / floor sinks), installation of new accessible door / hardware, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. Any racking installed exceeding 8 ft. in height will require a separate racking permit. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/15/2011 DONE
Drawings taken to records for scanning.
INSP-Final Inspection5/19/20115/20/20115/20/2011APASS
DetailsForrest France
Noted correction items field verified for completion. Functional testing passed, fire alarm permit finaled.
INSP-Final Inspection5/17/20115/18/20115/19/2011AFAIL
DetailsForrest France
Noted items include: incorrect or insufficient visual coverage at six locations due to cd settings on notification appliances which do not correlate with the plans, several wall mounted notification appliances along the length of the recieving/stock isles are beyond specified mounting heights allowed per NFPA 72 unless stipulations of the performance-based alternative can be met and documentation provided per conditions of the standard, noted four locations lacking visual coverage including the pharmacy waiting area, pharmacy patient consultation, bakery sales and bakery prep., need to verify db levels are met at the meat prep. room and the mech.areas. Pharmacy RR and the bank tenant space are not accessible for testing prior to 9:30 AM.
Inspection Record Card- Fire5/17/2011 5/17/2011 DONE
DetailsPatricia Smith
Telephone call  5/17/2011 DONE
customer here
Permit Ready to Issue  5/17/2011 DONE
Details
Issue and Print Permit  5/17/2011 DONE
Alarm Plan Check5/16/2011 5/16/2011 PASS
DetailsStephanie L. Cobbley
resubmitted plans approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  5/16/2011 DONE
Approved redlined plans available at front counter.
Plan assigned to (Stephanie)4/15/2011 5/16/2011 DONE
DetailsStephanie L. Cobbley
Plan resubmittals received  5/9/2011 DONE
DetailsChristina Prado
Received one copy of application and checklist; two copies of data sheets; one copy of PCI Inc review shhet; and two copies of plans FA-0.0, FA-1.0, FA-2.0 and FA-2.1. Routed to Spehanie for review
Telephone call  5/6/2011 DONE
Received a call from the engineer regarding changes he wanted to make to the re-submitted plans and stated that he had not yet had a chance to review the documents prior to them being submitted to me. I let him know I would not review the resubmittals until he could work out changes with the fire alarm contractor.
Telephone call  5/6/2011 DONE
Spoke to Joe with Allied General letting him know that the engineer had not had a chance to review the drawings and that I did not receive a letter indicating the review had taken place. Per the Findings of Fact, these plans should never have been taken in without the letter. Therefore, no review has been done. The second review will not take place until the engineer has a chance to review the resubmittals and make necessary changes/revisions. I asked Joe if he wanted to pick the plans back up, he said no to please recycle them.
Plan resubmittals received  5/4/2011 DONE
DetailsTisha Gallop
received application and three copies of submittal documents and plan sheets; routed to Fire Review.
Miscellaneous action  4/22/2011 DONE
contractor picked up failed plans
1st review completed  4/21/2011 DONE
Alarm Plan Check4/21/2011 4/21/2011 FAIL
DetailsStephanie L. Cobbley
Plans denied. See review comments and redlined plans
Miscellaneous action  4/21/2011 DONE
Called Joe at Allied General to let him know the plans are denied.
Miscellaneous action  4/21/2011 DONE
Faxed review comments to contractor
Miscellaneous action  4/21/2011 DONE
Denied plans and review comments available at front counter.
Application received  4/15/2011