Issue permit | | | 10/13/2011 | | DONE |
|
|
|
Payment received via Govolutions
|
Miscellaneous action | | | 10/13/2011 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 10/5/2011 | 10/5/2011 | 10/5/2011 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 10/4/2011 | 10/5/2011 | 10/5/2011 | A | PASS |
Forrest France
|
|
|
After hours reinspection passed, functional testing completed. C/N items and plan modifications verified.
|
INSP-Alarm Testing | 10/3/2011 | 10/3/2011 | 10/3/2011 | A | PART |
Forrest France
|
|
|
Ref. plans for areas inspected to date.
|
INSP-Alarm Testing | 9/29/2011 | 9/30/2011 | 9/30/2011 | A | PART |
Forrest France
|
|
|
As late as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian Anderson
|
INSP-Conference | 9/29/2011 | 9/29/2011 | 9/29/2011 | A | DONE |
Forrest France
|
|
|
Regarding plan modifications.
|
Override - Parcel Holds | | | 9/6/2011 | | |
|
|
|
|
Override - Parcel Holds | | | 9/6/2011 | | |
|
|
|
|
Inspection Record Card- Fire | 9/6/2011 | | 9/6/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 9/6/2011 | | DONE |
|
|
|
t/c w dante - permit (plan mod) ready and fees given
|
Override - Parcel Holds | | | 9/6/2011 | | |
|
|
|
|
Override - Parcel Holds | | | 9/6/2011 | | |
|
|
|
|
Permit Ready to Issue | | | 9/6/2011 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 9/6/2011 | | |
|
|
|
|
Override - Parcel Holds | | | 9/6/2011 | | |
|
|
|
|
Issue and Print Permit | | | 9/6/2011 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 8/19/2011 | | 9/2/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 9/2/2011 | | 9/2/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 9/2/2011 | | DONE |
|
|
|
Approved plan modification documents available at front counter.
|
Plan resubmittals received | | | 8/19/2011 | | DONE |
Tisha Gallop
|
|
|
Plan Modification: received two copies of application and plans, routed to Fire Review.
|
INSP-Conference | 8/2/2011 | 8/2/2011 | 8/2/2011 | A | DONE |
Forrest France
|
|
|
Regarding after hours inspection request 8/9 AM.
|
INSP-Final Inspection | 7/25/2011 | 7/25/2011 | 7/26/2011 | A | FAIL |
Forrest France
|
|
|
Correction items noted during after hours testing include; provide missing notification appliance in the package test chamber room, repair one corridor a/v adjacent to the NN room, relocated MP at one exit door is not finished due to pending work, two device address numbers are inconsistent with stamped plans, SD for door release have been deleted due to scope of work changes, one chamber and two notification devices at life test #2 have been moved. Provide plans reflecting actual scope of work completed including revised locations, addresses, circuts, etc.
|
INSP-Sprinkler Rough-in/Hydro | 7/8/2011 | 7/8/2011 | 7/8/2011 | P | PART |
Forrest France
|
|
|
Pre-inspection for work at life test #1 and the NN room completed.
|
Issue and Print Permit | | | 5/2/2011 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 4/25/2011 | | 4/29/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 4/29/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 4/29/2011 | | 4/29/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 4/29/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Inspection Record Card- Fire | 4/29/2011 | | 4/29/2011 | | DONE |
Patricia Smith
|
|
|
|
Permit Ready to Issue | | | 4/29/2011 | | DONE |
|
|
|
|
Application received | | | 4/25/2011 | | |
|
|
|
|