Permit NumberFIR11-00195
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1150 N CURTIS RD
Project NameBureau of Reclamation
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of recalculating the sprinkler system and changing piping to accommodate high piled rack storage. The existing 3” riser will be changed to a 4” riser.


Location on Plan - Various location
Commodity - Paper records and office equipment
Classification - Class III
Storage Type (rack, solid pile, etc.) - Racks
Pallet Type (wood or plastic) - Wood
Aisle Width - >8’
Height of Storage - 15’
Ceiling Height - 24’ but there is a large steel mezzanine
Encapsulated - No
Smoke and Heat Vents - No
Draft Curtain - No
In Rack Sprinklers - No
Sprinkler Type - SSU Large Orifice
High Temperature Sprinklers Required - Yes
NFPA Section - T 16.2.1.3.2, 16.2.1.3.2(c), F 16.2.1.3.4.1, T 16.2.1.3.5
Fire Protection Requirements - .222/2000 + 500 Hose


Building Department Scope:

At this time, there is no associated building permit or racking permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/22/20156/22/20156/22/2015PPASS
DetailsTroy Cobbley
Permit finaled
FIR-Aging Inspection6/16/20156/16/20156/22/2015 PASS
DetailsTroy Cobbley
FIR-Aging Inspection2/20/20132/20/20132/28/2013 DEFR
DetailsTroy Cobbley
I contacted Roy in Fire Prevention and he is going to follow up with the owner.
INSP-Conference10/10/201210/10/201210/10/2012PDONE
DetailsTroy Cobbley
I met with Steve, with the BLM, and we verified that the solid shelving had been removed and that the storage had been reduce to 15'-0". A racking permit is still required. I defered him to plan review for further information on this permit due to his engineer stating that a permit should not be required. Sent email to Scott.
FIR-Aging Inspection10/5/201210/5/201210/10/2012 NR
DetailsTroy Cobbley
See conference notes
FIR-Aging Inspection3/13/20123/13/20123/20/2012 NR
DetailsTroy Cobbley
I spoke to Charlie with SimplexGrinnel and he stated he would follow up on this project.
INSP-Sprinkler Rough-in/Hydro5/24/20115/25/20115/25/2011PPART
DetailsTroy Cobbley
The overhead hydro and sprinkler rough-in passed. The plans are approved for max. storage height of 15'. The current storage height is 17' and solid shelving with 2x4 supports are being utilized. So the storage arrangement needs to be permanantly modified or resubmittals are required. Also the project can not be finaled until a racking permit is applied for.
Telephone call  5/9/2011 DONE
DetailsTim Frost
Spoke with Brad at SimplexGrinnell. It appeared to me that the piping going to the FDC strictly fed just the FDC. The piping was 4", 3", 4". I thought the 3" was a typo since the entire main needed to be 4" due to having a 4" riser. However, the main is an express main for the system. The main is connected to both the primary and secondary mains. Therefore, the pipe sizing is fine. I asked Brad to mark his site drawing accordingly.
Plan assigned to (Tim)4/27/2011 5/2/2011 DONE
DetailsTim Frost
Sprinkler Plan Check5/2/2011 5/2/2011 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  5/2/2011 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  5/2/2011 DONE
DetailsTim Frost
Inspection Record Card- Fire5/2/2011 5/2/2011 DONE
DetailsPatricia Smith
Telephone call  5/2/2011 DONE
t/c w brad - permit ready and fees given
Permit Ready to Issue  5/2/2011 DONE
Details
Issue and Print Permit  5/2/2011 DONE
Application received  4/27/2011  
Case Summary  4/27/2011 DONE
DetailsBarbara Stitt