Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberFIR11-00197
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 11311 W CHINDEN BLVD
Project NameHP BLDG 7 SERVER ROOM VESDA
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a VESDA system in the server room for the area above and below the ceiling. An electrical room will be covered by smoke detection. Smoke detectors and the VESDA system will trigger a suppression release panel of the preaction system in the server room. Also part of this permit scope of work are relocated pull stations, new pull stations, and one AIM for the sprinkler system monitoring. Ceiling notification will notify the server room.

Associated building permit: BLD11-00544 (HEWLETT PACKARD BLDG 7 - IPG SERVER ROOM) - To remodel a 5,439 sq. ft. area (3 rooms) within an existing office / storage / shipping building, for current and future I.T. infrastructure growth. Work to include: demolition work per plans; install a new raised access floor system, a new ceiling system with relocated lighting, a new hydraulic lift for equipment and ADA access; construct interior UL listed walls, doors and associated hardware per plans; install a new suspended soffit and acoustical ceiling grid systems; frame new interior walls suspended from roof structure; install new exterior concrete pads w/ mechanical units and exhaust systems that will serve the I.T. room; construct new exterior concrete stairs with metal handrails and guards; provide new exterior fascia and wall panel finishes; interior finishes in compliance with chapter 8 of the 2009 IBC; modify the existing fire alarm/sprinkler system to meet tenants needs and be in compliance with current adopted codes. Work per the approved plans, Engineering, and all other reviewing agencies approvals. NOTE: This building is fully sprinklered with 60 foot yards all around for unlimited area based on current occupancy use. A "Letter of Completion / Compliance" is required as a condition of occupancy for this tenant improvement. DRH10-00308 **SRZ**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/2/2011 DONE
As-built drawings recieved
Miscellaneous action  9/2/2011 DONE
Taken to records for scanning.
INSP-Final Inspection8/1/20118/9/20118/9/2011APASS
DetailsForrest France
Fire alarm work passed after hours re-inspection. Permit finaled.
INSP-Sprinkler Rough-in7/25/20117/26/20117/27/2011ADONE
DetailsForrest France
Pre-inspection walkthrough completed for the fire alarm scope of work.
INSP-Final Inspection7/22/20117/25/20117/26/2011ANR
DetailsForrest France
After hours inspection incompleted due to notification appliances in need of adjustment and lack of access to the server room area.
Plan assigned to (Stephanie)5/3/2011 5/16/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  5/16/2011 DONE
Alarm Plan Check5/16/2011 5/16/2011 PASS
DetailsStephanie L. Cobbley
Approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  5/16/2011 DONE
Approved redlined plans available at front counter.
Inspection Record Card- Fire5/16/2011 5/16/2011 DONE
DetailsPatricia Smith
Telephone call  5/16/2011 DONE
left vm for charlie - permit ready and fees given
Permit Ready to Issue  5/16/2011 DONE
Details
Issue and Print Permit  5/16/2011 DONE
Application received  5/3/2011 DONE
DetailsBarbara Stitt