Miscellaneous action | | | 9/22/2011 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 8/30/2011 | 8/31/2011 | 8/31/2011 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in | 5/31/2011 | 5/31/2011 | 5/31/2011 | P | PART |
Forrest France
|
|
|
Cold cavity protection verified. Overhead fire sprinkler installation approved for cover.
|
INSP-Sprinkler Rough-in | 5/16/2011 | 5/17/2011 | 5/17/2011 | A | PART |
Forrest France
|
|
|
Overhead rough-in passed inspection- one additional head to be installed at under stairway storage room, noted field mods at branch line routing okayed. Cover approval pending satisfactory tenting and insulation inspection prior to sheetrock.
|
Issue and Print Permit | | | 5/11/2011 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 5/5/2011 | | 5/9/2011 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 5/9/2011 | | DONE |
Tisha Gallop
|
|
|
contractor picked up denied plans
|
Meeting | | | 5/9/2011 | | DONE |
Tim Frost
|
|
|
Meeting with Don Curtis.
I apparently misread the sprinkler information data sheet. The 13Gpm@7Psi is good for up to 16'x16' spacing. Therefore, comment 1 is resolved.
Don, and I discuss comment 2. Don thought since this is a 13D system that the cross main did not need to be protected. I told him I understood his postion but that I disagreed. The main is in an unprotected crawl space and it is plastic pipe. I told him that he needed to add sprinklers or move the main. I also said NFPA 13D references NFPA 13 which has this requirment. He agreed to add the sprinklers.
|
Plan resubmittals received | | | 5/9/2011 | | DONE |
Christina Prado
|
|
|
Received three sets of application, both checklists, spec sheets, resubmittal responce and plans FP1-1. Routed to Tim Frost for additional review
|
Sprinkler Plan Check | 5/9/2011 | | 5/9/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/9/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 5/9/2011 | | 5/9/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 5/9/2011 | | DONE |
|
|
|
t/c w don - permit ready and fees given
|
Permit Ready to Issue | | | 5/9/2011 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/6/2011 | | 5/6/2011 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 5/6/2011 | | DONE |
Tim Frost
|
|
|
|
Telephone call | | | 5/6/2011 | | DONE |
|
|
|
t/c w don - permit denied - needs to be picked up and resubmitted
|
Application received | | | 5/5/2011 | | |
|
|
|
|