Case Summary | | | 4/4/2014 | | DONE |
|
|
|
|
INSP-Final Inspection | 2/20/2014 | 2/21/2014 | 2/21/2014 | A | PASS |
Forrest France
|
|
|
Remainder of fire alarm work and testing completed acceptable. Permit finaled.
|
FIR-Aging Inspection | 3/15/2013 | 3/15/2013 | 3/21/2013 | | DONE |
Forrest France
|
|
|
|
FIR-Aging Inspection | 8/28/2012 | 8/28/2012 | 8/28/2012 | | DEFR |
Forrest France
|
|
|
|
FIR-Aging Inspection | 4/27/2012 | 4/27/2012 | 4/27/2012 | | PART |
Forrest France
|
|
|
Okay to final when elevator recall functions are verified.
|
INSP-Final Inspection | 10/3/2011 | 10/3/2011 | 10/3/2011 | P | CANC |
Troy Cobbley
|
|
|
Overbooked.
Rod or Brian #: ###-####
|
INSP-Conference | 9/26/2011 | 9/26/2011 | 9/26/2011 | P | DONE |
Forrest France
|
|
|
Regarding elevator recall functions.
|
INSP-Alarm Testing | 9/16/2011 | 9/22/2011 | 9/22/2011 | A | PART |
Forrest France
|
|
|
Items on previous inspection notes verified for completion. Permit final pending elevator recall functions.
|
INSP-Alarm Testing | 8/31/2011 | 9/6/2011 | 9/6/2011 | A | PART |
Forrest France
|
|
|
Noted correction items include; breaker lock at the panel, signage at doors to the FACP room, remove two non-functional existing SD, post points map at the panel, relocate two MP stations to no higher than 48" AFF, add visual coverage at the copy room 1st floor, provide letter regarding elevator. Items tested today include notification throughout, all HD and MP, panel conditons, sprinkler monitoring, duct detectors, and beam detectors. Settings at two notification appliances adjusted while on site.
|
Plan assigned to (Stephanie) | 5/25/2011 | | 6/6/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 6/6/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 6/6/2011 | | 6/6/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Approved - see review comments and redlines
|
PLANS TAKEN FRONT DESK ALARM | | | 6/6/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Permit Ready to Issue | | | 6/6/2011 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 6/6/2011 | | 6/6/2011 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 6/6/2011 | | DONE |
Barbara Stitt
|
|
|
Called Charlie and told him that permit is ready 6-6-11 @ 3:00pm///BAS
|
Issue and Print Permit | | | 6/6/2011 | | DONE |
Tisha Gallop
|
|
|
|
Application received | | | 5/25/2011 | | |
|
|
|
|