INSP-Final Inspection | 4/17/2012 | 4/17/2012 | 4/19/2012 | P | PASS |
Forrest France
|
|
|
C/N items verified. Fire alarm permit finaled.
|
INSP-Final Inspection | 4/11/2012 | 4/11/2012 | 4/12/2012 | A | PART |
Forrest France
|
|
|
Revision items include; junction box covers, labels at a/v's, remove sample piping at deleted vesda zone 3, relocate smoke detectors for door release service per NFPA 72 at two locations, fire curtain closure rate to comply with NFPA 80 guidelines.
|
FIR-Aging Inspection | 3/22/2012 | 3/22/2012 | 3/22/2012 | | DONE |
Forrest France
|
|
|
In progress
|
Issue and Print Permit | | | 6/13/2011 | | DONE |
|
|
|
|
1st review completed | | | 6/3/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 6/3/2011 | | 6/3/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Approved with redlines - no written review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 6/3/2011 | | DONE |
|
|
|
|
Miscellaneous action | | | 6/3/2011 | | DONE |
|
|
|
Review done and plans given to T. Cobbley for delivery to Micron
|
Application received | | | 5/26/2011 | | DONE |
Mary Froemke
|
|
|
This permit was created on the web by Paul Marcolina
|
Application received | | | 5/26/2011 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|