Miscellaneous action | | | 9/22/2011 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 9/19/2011 | 9/20/2011 | 9/19/2011 | A | PASS |
Troy Cobbley
|
|
|
permit finaled. owner is removing the palm fronds that are blocking the sidewall protection in the seating area.
|
INSP-Sprinkler Rough-in | 7/7/2011 | 7/8/2011 | 7/8/2011 | A | PASS |
Troy Cobbley
|
|
|
The piping in the modified soffit area is ok to cover.
|
INSP-Sprinkler Rough-in | 7/5/2011 | 7/5/2011 | 7/6/2011 | P | PART |
Troy Cobbley
|
|
|
Rough-in passed but piping has been modified in the Buffett area to sidewall coverage that has been installed in a large soffit. Contractor to get with Tim Frost on possible plan modifications due to the changes. Piping is ok to cover except in this area. Additional dry pendants are to be added in the three coolers to provide coverage behind the coil units.
|
Issue and Print Permit | | | 6/6/2011 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/3/2011 | | 6/3/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/3/2011 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 6/3/2011 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 6/3/2011 | | 6/3/2011 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 6/3/2011 | | DONE |
Barbara Stitt
|
|
|
Left a message for Broadie that permit is ready and fees due on 6-3-11 @ 3:33pm
|
Plan assigned to (Tim) | 5/26/2011 | | 6/3/2011 | | DONE |
Tim Frost
|
|
|
|
Plan resubmittals received | | | 6/2/2011 | | |
Barbara Stitt
|
|
|
|
Miscellaneous action | | | 6/1/2011 | | DONE |
|
|
|
Received the remaining missing information today. Proceeding, with review.
|
Sprinkler Plan Check | 6/1/2011 | | 6/1/2011 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 6/1/2011 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 6/1/2011 | | DONE |
|
|
|
Emailed review to contractor
|
Telephone call | | | 6/1/2011 | | DONE |
|
|
|
t/c w brodie - permit denied - needs to be picked up and resubmitted
|
Miscellaneous action | | | 5/27/2011 | | DONE |
|
|
|
Email Brodie a RFI.
|
Application received | | | 5/26/2011 | | |
|
|
|
|