Permit EXPIRED | | | 1/2/2019 | | DONE |
|
|
|
Per Jeremy Berg, see documents for email.
|
FIR-Aging Inspection | 9/9/2014 | 9/9/2014 | 9/9/2014 | | PEND |
Forrest France
|
|
|
Refer to inspection notes 12/12/11 for correction items.
|
FIR-Aging Inspection | 3/21/2013 | 3/21/2013 | 3/21/2013 | | PEND |
Forrest France
|
|
|
|
FIR-Aging Inspection | 12/20/2012 | 12/20/2012 | 12/20/2012 | | PEND |
Forrest France
|
|
|
|
FIR-Aging Inspection | 9/20/2012 | 9/20/2012 | 9/20/2012 | | DONE |
Forrest France
|
|
|
wip
|
FIR-Aging Inspection | 6/21/2012 | 6/21/2012 | 6/21/2012 | | NR |
Forrest France
|
|
|
Pending correction items.
|
FIR-Aging Inspection | 3/22/2012 | 3/22/2012 | 3/22/2012 | | PEND |
Forrest France
|
|
|
Pending correction items dated 12/12/11.
|
INSP-Final Inspection | 12/12/2011 | 12/12/2011 | 12/12/2011 | P | FAIL |
Troy Cobbley
|
|
|
Provide strobe modifications as discussed to provide coverage in the deficient areas. All of the strobes in the shop areas are mounted too high. The need to meet NFPA 72 mounting heights, go with the performance based design (lighting calculations) or take it up with the fire marshal. As-builts need to be provided showing the strobe modifications and one additional pull station. This is to include revised one line and EOL calculations. Signals were sent out on phone line #1 but not phone line #2 so that needs to be tested as well. We discussed the phone lines as possibly be ground start and not loop start as required per NFPA 72 26.6.3.2.1.1. When the contractor calls my phone the same number comes up and he must dial "9" first.
|
INSP-Final Inspection | 12/6/2011 | 12/8/2011 | 12/12/2011 | A | CANC |
Troy Cobbley
|
|
|
Rescheduled for 12/12/2011
|
Issue and Print Permit | | | 6/16/2011 | | DONE |
|
|
|
|
Telephone call | | | 6/13/2011 | | DONE |
Barbara Stitt
|
|
|
Called and told Shayla that permit is ready & fees due on 6-13-11 @ 8:30am//BAS
|
Plan assigned to (Stephanie) | 6/3/2011 | | 6/10/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 6/10/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 6/10/2011 | | 6/10/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 6/10/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Permit Ready to Issue | | | 6/10/2011 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 6/10/2011 | | 6/10/2011 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 6/3/2011 | | |
|
|
|
|