Miscellaneous action | | | 9/22/2011 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 7/22/2011 | 7/22/2011 | 7/22/2011 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled. C/N items verified. Note: Per contractor survey, head count in this building is 97.
|
INSP-Final Inspection | 7/20/2011 | 7/21/2011 | 7/21/2011 | A | PART |
Forrest France
|
|
|
Final pending four missing escutcheons at the west lobby, mens restroom and RR vestibule.
|
INSP-Sprinkler Rough-in | 7/6/2011 | 7/7/2011 | 7/7/2011 | A | PART |
Forrest France
|
|
|
Overhead work approved for cover with the exception of one overspaced hanger at an armover in the kitchen area- See plans for marked location.
|
(F) Reprint permit | | | 6/29/2011 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 6/29/2011 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 6/27/2011 | | 6/28/2011 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 6/28/2011 | | 6/28/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 6/28/2011 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/28/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 6/28/2011 | | 6/28/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 6/28/2011 | | DONE |
|
|
|
t/c w teresa - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 6/28/2011 | | DONE |
|
|
|
|
Plan resubmittals received | | | 6/27/2011 | | |
|
|
|
|
Issue and Print Permit | | | 6/9/2011 | | DONE |
|
|
|
|
Application received | | | 6/7/2011 | | |
|
|
|
|
Plan assigned to (Tim) | 6/7/2011 | | 6/7/2011 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 6/7/2011 | | 6/7/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 6/7/2011 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/7/2011 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 6/7/2011 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 6/7/2011 | | 6/7/2011 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 6/7/2011 | | DONE |
Barbara Stitt
|
|
|
Called and told Teresa that plans were ready & fees due on 6-7-11 @ 1:40pm//BAS
|
Telephone call | | | 6/7/2011 | | DONE |
Barbara Stitt
|
|
|
Called Charlie and told him that permit is ready on 6-7-11 @ 1:45pm//BAS
|