Miscellaneous action | | | 10/13/2011 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 10/7/2011 | 10/7/2011 | 10/7/2011 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled.
|
Miscellaneous action | | | 10/6/2011 | | DONE |
|
|
|
Asbuilt documents received
|
Plan resubmittals received | | | 10/6/2011 | | DONE |
|
|
|
received one copy of small docs for PAM (3 pgs); routed to Fire Review
|
INSP-Alarm Testing | 10/4/2011 | 10/4/2011 | 10/4/2011 | P | FAIL |
Troy Cobbley
|
|
|
Provide as-builts showing the wiring schematic for the PAM-2 relay that has been added to provide an alarm output to the AES. Also provide a data sheet for the PAM-2 relay. Permit can be finaled when this documentation has been provided.
|
INSP-Final Inspection | 6/30/2011 | 7/1/2011 | 7/1/2011 | A | CANC |
Troy Cobbley
|
|
|
Shielded wire needs to be installed and the correct transformer. No inspection was performed.
|
Issue and Print Permit | | | 6/30/2011 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/15/2011 | | 6/15/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 6/15/2011 | | DONE |
|
|
|
t/c w jessica - permit ready and fees given
|
Permit Ready to Issue | | | 6/15/2011 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 6/9/2011 | | 6/14/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 6/14/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 6/14/2011 | | 6/14/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 6/14/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Application received | | | 6/9/2011 | | |
|
|
|
|