Permit Information
Permit NumberFIR11-00292
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 321 S 8TH ST
Project NameFive Guy Burg BODO BLDG #4
Customer Number 
ePlanReviewNo
Description
Quick Permit
Add and relocate sprinklers to accommodate new wall and ceiling arrangment.

(FIVE GUYS BURGER AND FRIES - BODO BUILDING #4 - 1ST STORY) (6-13-11 PLAN MODIFICATION TO CHANGE THE ROUTING AND SHAFT SYSTEM FOR THE GREASE DUCT. INSTEAD OF PENETRATING A 2-HR FIRE WALL, THE GREASE DUCT WILL BE KEPT INSIDE THE BUILDING UNTIL IT PENETRATES THE ROOF. IN LIEU OF USING A FACTORY-BUILT GREASE DUCT ASSEMBLY THAT INCORPORATES INTEGRAL ENCLOSURE MATERIALS, A FIELD-APPLIED 2 LAYER DUCT WRAP SYSTEM WILL BE INSTALLED ON THE OUTSIDE OF THE GREASE DUCT. FOR MUCH OF ITS LENGTH, THE ENTIRE ASSEMBLY WILL BE ENCLOSED WITHIN A 1-HR SHAFT. LISTING INFORMATION FOR THE 2 LAYER DUCT WRAP SYSTEM AND FOR THE 1-HR SHAFT SHALL BE PROVIDED TO THE STRUCTURAL INSPECTOR. THE 2 LAYER DUCT WRAP SYSTEM IS REQUIRED TO REDUCE CLEARANCES AND THE 1-HR SHAFT IS REQUIRED TO AVOID A THROUGH PENETRATION FIRE STOP SYSTEM.) Fire sprinklers used for building area increase and for fire area. To convert an existing 2,600 square foot tenant space into a restaurant. Work is to include 2 restrooms accessible to the disabled, interior nonbearing walls, suspended acoustical ceilings, 2 grease hoods, a 2-hr grease duct that penetrates a 2 hour fire wall, kitchen equipment, and interior finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/16/20116/17/20116/17/2011APASS
DetailsForrest France
Fire sprinkler permit final approved.
INSP-Final Inspection6/15/20116/16/20116/16/2011APART
DetailsForrest France
Overhead fire sprinkler system modifications above the drop ceilings approved for cover.
Plan assigned to (Tim)6/14/2011 6/15/2011 DONE
DetailsTim Frost
Sprinkler Plan Check6/15/2011 6/15/2011 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  6/15/2011 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  6/15/2011 DONE
DetailsTim Frost
Inspection Record Card- Fire6/15/2011 6/15/2011 DONE
DetailsPatricia Smith
Telephone call  6/15/2011 DONE
t/c w brodie - permit ready and fees given
Permit Ready to Issue  6/15/2011 DONE
Details
Issue and Print Permit  6/15/2011 DONE
DetailsBarbara Stitt
Application received  6/14/2011  
Pending Assignment by SAM6/14/2011 6/14/2011 DONE
DetailsPatricia Smith