Permit Information
Permit NumberFIR11-00301
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 8000 S FEDERAL WAY
Project NameB50-R&D EXPANSION BLD
Customer NumberC15044
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of system 8 ONLY. This system protects approximately half of the subfab area (lower level). The sprinklers are space at the junction of the concrete waffle construction. The system is a 4”x4”x1½” grid. The system is supplied by two 8” connections to a 10” loop underground. The two 8” lead ins are equipped with a yard PIV. A free standing FDC on top of a pit is also included in this scope of work. There is additional fire protection below three large ducts running east to west due to obstruction issues.

Plan Mod #1
The underground supply feeding the north riser was changed from a loop supply into the building to a dead end feed into the building. The north riser was revised accordingly.


Building Department Scope:

Micron Building B50 - R&D Building - To construct a new 111,005 square foot, two story, with 71,855 square foot basement, concrete and steel semiconductor fabrication R & D facility and related site improvements. The first floor level is 89,435 sq. ft. (60,100 sq. ft. finished and 29,325 sq. ft. unfinished). The second floor is a 21,570 sq. ft. mechanical space (16,170 sq. ft. used and 5,400 square feet future). The basement level (subfab.) has 43,295 sq. ft. finished and 28,560 unfinished. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/23/2013 DONE
DetailsTim Frost
Sent to Records for scanning.
INSP-Final Inspection11/20/201211/20/201211/20/2012APASS
DetailsForrest France
INSP-Final Inspection10/22/201210/22/201210/30/2012PPEND
DetailsForrest France
Ref. activity notes.
INSP-Final Inspection10/17/201210/19/201210/30/2012APART
DetailsForrest France
Noted overspaced coverage at one location below ductwork at the junction between sub fab systems, provide verification AE and FE ductwork does not require protection per IFC 2009 1803.10.4 (1-3).
FIR-Aging Inspection8/28/20128/28/20128/28/2012 DEFR
DetailsForrest France
INSP-Supply line flush5/29/20125/30/20125/30/2012PPART
DetailsForrest France
UG fire supply line flush for the SW building riser and remote FDC completed satisfactory.
INSP-Sprinkler Rough-in4/10/20124/11/20124/12/2012PNR
DetailsForrest France
INSP-Sprinkler Rough-in4/2/20124/3/20124/4/2012PPART
DetailsForrest France
Vestibules 000B and 002B are incomplete. Plan modifications pending.
INSP-Sprinkler Rough-in/Hydro3/30/20124/2/20124/2/2012PPART
DetailsForrest France
Overhead hydrostatic test passed.
INSP-Sprinkler Rough-in/Hydro3/29/20123/30/20123/30/2012PNR
DetailsForrest France
INSP-Sprinkler Rough-in/Hydro3/28/20123/29/20123/30/2012AFAIL
DetailsForrest France
Overhead hydrostatic test failed due to pressure loss at the gauge.
INSP-Sprinkler Rough-in/Hydro2/28/20122/29/20123/1/2012PPART
DetailsForrest France
Re-inspection for corrections system 8 sub fab include the following locations: added coverage at extended ductwork, over spacing at sub fab mechanical, coverage added at the catwalk and soffits between elevator machine room 001A and communication room 001B.
INSP-Sprinkler Rough-in/Hydro2/20/20122/21/20122/22/2012APART
DetailsForrest France
System 8 sub fab reinspection items include spacing at the temporary wall is 7'-6", four obstructed uprights adjacent to temporary unistrut trapeeze members, added outlet for chemical cabinets not shown on plans, missing potter air vent per drawings, added vestibules 000B and 002B including fire protection are not included on plans, sheetrock soffit enclosure at the new catwalk creates obstructions in three areas, need to add coverage under newly extended ductwork over 4', missing intermediate hangers under both stairways. Noted overspaced uprights under ductwork system 8 mechanical. Previous c/n items at some areas have been completed. Also noted quantities of sodium hypochlorite, sulfuric acid, process water, DI and IW located within the building.
INSP-Sprinkler Rough-in1/11/20121/12/20121/12/2012APART
DetailsForrest France
UG fire supply line flush at the NW riser feed completed satisfactory.
INSP-Supply line flush1/10/20121/11/20121/11/2012PNR
DetailsForrest France
Contractor unable to complete supply line flushing at the NW riser due to jobsite conditions.
INSP-Sprinkler Rough-in/Hydro11/22/201111/23/201111/23/2011PNR
DetailsForrest France
Please contact Jeremiah prior to arrival. Phone #: ###-#### >> Inspection requested via web by Alicia Pauley NOTE: **Area requested for inspection is not included in the scope of this permit (FIR11-00301 covers system 8 sub-fab). Contractor intended an overhead inspection for system 4 photo bay for which permit FIR11-00524 is not yet approved or issued at this time. Noted system 4 mains and branchlines already installed. No inspection performed due to permit status and lack of approved drawings.**
INSP-Sprinkler Rough-in11/21/201111/21/201111/21/2011PPART
DetailsForrest France
UG fire supply line and remote FDC piping at the NW corner inspected prior to cover. Contractor has installed mechanical joint restraints in place of thrust blocks.
INSP-Sprinkler Rough-in/Hydro11/18/201111/21/201111/21/2011APART
DetailsForrest France
UG hydrostatic test for the NW fire supply line and remote FDC piping completed satisfactory.
INSP-Sprinkler Rough-in/Hydro11/18/201111/18/201111/18/2011PNR
DetailsForrest France
Please call Jeremiah prior arrival to confirm. Phone #: ###-#### >> Inspection requested via web by Alicia Pauley
INSP-Sprinkler Rough-in11/14/201111/15/201111/15/2011APART
DetailsForrest France
UG fire supply line and remote FDC piping at the SE corner okayed to bury. Note: contractor has utilized a restrained joint system per NFPA 13 10.8.3 in place of thrust blocking. Discussed bury depth requirements with contractor per civil drawing elevations- UG pipe to be maintained 4'6" below grade min.
INSP-Sprinkler Rough-in/Hydro11/11/201111/14/201111/14/2011APART
DetailsForrest France
UG fire supply line and remote FDC piping at the SE corner of building 50 passed hydrostatic test.
INSP-Sprinkler Rough-in/Hydro11/9/201111/10/201111/10/2011AFAIL
DetailsTroy Cobbley
tony please call 1/2 hr prior Phone #: ###-####

Contacted tony and let him know I was on the way. I arrived and found that the water had not been turned on for tony to pump up the underground. No testing was performed.
Fees Due Hold10/13/2011 10/14/2011 DONE
DetailsDarla L Downs
CHANGE STATUS TO (ISS)  8/26/2011 DONE
Sprinkler Plan Check8/24/2011 8/24/2011 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  8/24/2011 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  8/24/2011 DONE
DetailsTim Frost
Inspection Record Card- Fire8/24/2011 8/24/2011 DONE
DetailsPatricia Smith
Telephone call  8/24/2011 DONE
left vm for bob - permit (plan mod) ready and fees given
Permit Ready to Issue  8/24/2011 DONE
Details
INSP-Conference8/12/20118/15/20118/15/2011ADONE
DetailsForrest France
On site conference with contractor regarding project design, installation, schedule, etc.
Miscellaneous action  7/26/2011 DONE
Please, see below email regarding piping without continuous marking.

Ken,

Concerning the issue with 4” galvanized Schedule 40 pipe in area 8 at Micron Building 50. The pipe is supposed to be marked every 24” with manufacturing and listing data according to NFAP 13.

As per the documented Mill Report that indicates the 4” ASTM A53 Grade A Schedule 40 pipe passed the UL inspection and this particular batch of pipe was designated Heat #11123 and that the tags noted indicate that the pipe is ASTM A53 Grade A Schedule 40 and a UL symbol is on the tag and the tag also indicates that each of the 3 lifts is part of Heat #11123.

I believe this information is sufficient to be an alternative to the required markings and approve of the use of this pipe.


Thank You,





Ron Amandus



Interim Fire Marshal


Fire Prevention Division

Boise Fire Department



333 N. Mark Stall Place

Boise, Idaho 83###-####

###-####
Issue and Print Permit  7/1/2011 DONE
DetailsBarbara Stitt
Plan assigned to (Tim)6/23/2011 6/29/2011 DONE
DetailsTim Frost
Telephone call  6/29/2011 DONE
Spoke with Paul. He said the panels were non combustible aluminum. There will be a vesda detection system and smoke detection system. The smoke detection will be in the ductwork. They will be cross zoned.
Telephone call  6/29/2011 DONE
Talked with John Ronan and Paul. John informed me that the space below the raised floor would be non-combustible or limited combustible. Special composite materials are being utilized. I asked him about the 200 degree intermediate temperture sprinklers. He agreed that they should be regular temperture sprinklers not intermediate.
Sprinkler Plan Check6/29/2011 6/29/2011 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  6/29/2011 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  6/29/2011 DONE
DetailsTim Frost
Inspection Record Card- Fire6/29/2011 6/29/2011 DONE
DetailsPatricia Smith
Telephone call  6/29/2011 DONE
left vm for bob - permit ready and fees given
Permit Ready to Issue  6/29/2011 DONE
Details
Miscellaneous action  6/28/2011 DONE
Sent Paul an email and told him I still have not heard back from him in regards to the panels and flooring.
Telephone call  6/27/2011 DONE
I called Paul at Micron on Friday and left a voice mail. I called Paul at Micron again this morning. I asked him to tell me if the "1" Walkable Clean Room panels were combustible. He told me he would email me with the information. He also told me that he thought the panels and the floor above was perforated. I told him I was concerned that the response time of the sprinklers would be significantly impacted.
Application received  6/23/2011