Miscellaneous action | | | 9/6/2011 | | DONE |
|
|
|
Taken to records for scanning.
|
INSP-Final Inspection | 8/11/2011 | 8/12/2011 | 8/12/2011 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 8/9/2011 | 8/11/2011 | 8/11/2011 | A | FAIL |
Troy Cobbley
|
|
|
HVAC units 213 and 214 did not shut down immediately upon detection of smoke. All other devices tested ok.
|
INSP-Final Inspection | 8/8/2011 | 8/8/2011 | 8/8/2011 | P | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for redline corrections. No devices have been tested except for main level audibility which was ok.
|
INSP-Final Inspection | 8/4/2011 | 8/5/2011 | 8/5/2011 | P | CANC |
Troy Cobbley
|
|
|
To be rescheduled for monday per phone conversation with colton Phone #: ###-####
|
Plan assigned to (Stephanie) | 6/23/2011 | | 6/28/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 6/28/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 6/28/2011 | | 6/28/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 6/28/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Inspection Record Card- Fire | 6/28/2011 | | 6/28/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 6/28/2011 | | DONE |
|
|
|
left vm for dante - permit ready and fees given
|
Permit Ready to Issue | | | 6/28/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/28/2011 | | DONE |
|
|
|
|
Telephone call | | | 6/24/2011 | | DONE |
|
|
|
Spoke with Chris B. at SimplexGrinnell regarding the lack of smoke detection coverage in the remodeled area. He asked if I could hold off on the review until Monday 6/27 when Charlie Bayne is back and could better answer my questions.
|
Application received | | | 6/23/2011 | | |
|
|
|
|