Miscellaneous action | | | 9/22/2011 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 9/6/2011 | 9/7/2011 | 9/7/2011 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit work passed final inspection.
|
INSP-Final Inspection | 9/2/2011 | 9/2/2011 | 9/2/2011 | P | FAIL |
Forrest France
|
|
|
Final pending repair of three non-functional waterflow switches at the new riser manifold.
|
INSP-Sprinkler Rough-in/Hydro | 8/12/2011 | 8/12/2011 | 8/12/2011 | P | PART |
Forrest France
|
|
|
Hydrostatic testing passed for the new wet system manifolds and piping.
|
INSP-Sprinkler Rough-in/Hydro | 8/12/2011 | 8/12/2011 | 8/12/2011 | A | PART |
Forrest France
|
|
|
Overhead rough-in for the new dry system completed. Noted items include; replace three BB1 attic heads due to modified deflector/frame orientation, one upright head at the NE dormer is obstructed by truss webs, one EQ brace secured while on site.
|
INSP-Sprinkler Rough-in/Hydro | 8/10/2011 | 8/11/2011 | 8/12/2011 | A | PART |
Forrest France
|
|
|
Completed satisfactory 24 hr. air test of the new dry system piping.
|
INSP-Final Inspection | 8/9/2011 | 8/10/2011 | 8/10/2011 | A | PART |
Forrest France
|
|
|
Begin 24 hr. air test of the new dry system piping at 11:30 AM @44.5psig.
|
INSP-Sprinkler Rough-in/Hydro | 8/8/2011 | 8/9/2011 | 8/9/2011 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic testing for the new dry system piping passed. Discussed schedule for pneumatic test.
|
Plan assigned to (Tim) | 6/29/2011 | | 7/11/2011 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 7/11/2011 | | 7/11/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/11/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 7/11/2011 | | 7/11/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 7/11/2011 | | DONE |
|
|
|
t/c w melissa - permit ready and fees given
|
Permit Ready to Issue | | | 7/11/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/11/2011 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/8/2011 | | DONE |
Christina Prado
|
|
|
Received 4 new sets of applications, checklists, calcs and plan sheet 1 of 1. Routed to Tim Frost for additional review
|
Sprinkler Plan Check | 6/30/2011 | | 6/30/2011 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 6/30/2011 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 6/30/2011 | | DONE |
|
|
|
Emailed Contractor Reivew.
|
Telephone call | | | 6/30/2011 | | DONE |
|
|
|
t/c w brett - permit denied - needs to be picked up and resubmitted
|
Application received | | | 6/29/2011 | | |
|
|
|
|