Miscellaneous action | | | 1/20/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 12/14/2011 | 12/16/2011 | 12/16/2011 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The old devices were being removed when I left.
|
CHANGE STATUS TO (ISS) | | | 11/1/2011 | | DONE |
Barbara Stitt
|
|
|
|
(F) Reprint permit | | | 11/1/2011 | | DONE |
Barbara Stitt
|
|
|
|
Alarm Plan Check | 10/31/2011 | | 10/31/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification plans approved with review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 10/31/2011 | | DONE |
|
|
|
Approved plan modification documents available at front counter.
|
Inspection Record Card- Fire | 10/31/2011 | | 10/31/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 10/31/2011 | | DONE |
|
|
|
t/c w neal - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 10/31/2011 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 9/15/2011 | | 10/31/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan resubmittals received | | | 10/25/2011 | | DONE |
|
|
|
Received two new sets of application, checklist, calcs and plans. Routed to Stephanie for review
|
Alarm Plan Check | 9/27/2011 | | 9/27/2011 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - please see redlines and review comments.
|
Telephone call | | | 9/27/2011 | | DONE |
|
|
|
Called the contractor's office and left a message that the plans are denied and they can pick up the redlines from the front desk.
|
Miscellaneous action | | | 9/27/2011 | | DONE |
|
|
|
Faxed a copy of the review comments to the contractor.
|
Miscellaneous action | | | 9/27/2011 | | DONE |
|
|
|
Denied plans available at front counter for contractor to pick up.
|
Plan resubmittals received | | | 9/15/2011 | | DONE |
Tisha Gallop
|
|
|
Plan Modification: Received two copies of application, submittal folder and plans; routed to Fire Review.
|
INSP-Final Inspection | 7/13/2011 | 7/18/2011 | 7/18/2011 | A | FAIL |
Troy Cobbley
|
|
|
Provide plan modifications showing the notification devices located on the correct circuits and the corrected candellas. Provide correct data sheets for the devices actually installed. The audible notification devices utilized a solid tone, not temporal. Research indicated that the fire alarm system was updated after the requirement for the temporal sound. Documentation needs to be provided indicating otherwise or the audible sound needs to be modified.
|
Issue and Print Permit | | | 7/11/2011 | | DONE |
|
|
|
|
Application received | | | 7/1/2011 | | |
|
|
|
|
Plan assigned to (Stephanie) | 7/1/2011 | | 7/1/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 7/1/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 7/1/2011 | | 7/1/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Approved with review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 7/1/2011 | | DONE |
|
|
|
Approved plans available at front counter.
|
Inspection Record Card- Fire | 7/1/2011 | | 7/1/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 7/1/2011 | | DONE |
|
|
|
left vm for erin - permit ready and fees given
|
Permit Ready to Issue | | | 7/1/2011 | | DONE |
|
|
|
|