Permit Information
Permit NumberFIR11-00313
StatusFinaled
Name M2 AUTOMATION
Site Address 150 N CAPITOL BLVD
Project NameCITY HALL BLDG #1 4TH FLOOR
Customer Number 
ePlanReviewNo
Description
9-27-11 PLAN MODIFICATION (no initiating devices affected): This plan modification is to upgrade the 4th floor notification devices to achieve Temporal Code, as per the requirements during the time of initial system install.
7-1-11: This fire alarm permit is to provide notification to accommodate a new break room and tie it in to the existing fire alarm system.
Associated building permit: BLD04-02149 (PUBLIC WORKS ADMIN) (Building #1, 4th Floor) A "Letter of Compliance" is required. The building is fully sprinklered. To perform selective demolition per plan to enlarge 119 sq. ft. existing room. To construct 16' - 5" of new wall with access door to create a 128 sq. ft. private work room; cabinetry and shelving being relocated to the new room; and electrical for tenant needs and minimum code. Filed review and approval required by fire code inspector. PC04-594/drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  1/20/2012 DONE
Plans taken to records for scanning.
INSP-Final Inspection12/14/201112/16/201112/16/2011APASS
DetailsTroy Cobbley
Permit finaled. The old devices were being removed when I left.
CHANGE STATUS TO (ISS)  11/1/2011 DONE
DetailsBarbara Stitt
(F) Reprint permit  11/1/2011 DONE
DetailsBarbara Stitt
Alarm Plan Check10/31/2011 10/31/2011 PASS
DetailsStephanie L. Cobbley
Plan modification plans approved with review comments
PLANS TAKEN FRONT DESK ALARM  10/31/2011 DONE
Approved plan modification documents available at front counter.
Inspection Record Card- Fire10/31/2011 10/31/2011 DONE
DetailsPatricia Smith
Telephone call  10/31/2011 DONE
t/c w neal - permit (plan mod) ready and fees given
Permit Ready to Issue  10/31/2011 DONE
Details
Plan assigned to (Stephanie)9/15/2011 10/31/2011 DONE
DetailsStephanie L. Cobbley
Plan resubmittals received  10/25/2011 DONE
Received two new sets of application, checklist, calcs and plans. Routed to Stephanie for review
Alarm Plan Check9/27/2011 9/27/2011 FAIL
DetailsStephanie L. Cobbley
Plans denied - please see redlines and review comments.
Telephone call  9/27/2011 DONE
Called the contractor's office and left a message that the plans are denied and they can pick up the redlines from the front desk.
Miscellaneous action  9/27/2011 DONE
Faxed a copy of the review comments to the contractor.
Miscellaneous action  9/27/2011 DONE
Denied plans available at front counter for contractor to pick up.
Plan resubmittals received  9/15/2011 DONE
DetailsTisha Gallop
Plan Modification: Received two copies of application, submittal folder and plans; routed to Fire Review.
INSP-Final Inspection7/13/20117/18/20117/18/2011AFAIL
DetailsTroy Cobbley
Provide plan modifications showing the notification devices located on the correct circuits and the corrected candellas. Provide correct data sheets for the devices actually installed. The audible notification devices utilized a solid tone, not temporal. Research indicated that the fire alarm system was updated after the requirement for the temporal sound. Documentation needs to be provided indicating otherwise or the audible sound needs to be modified.
Issue and Print Permit  7/11/2011 DONE
Application received  7/1/2011  
Plan assigned to (Stephanie)7/1/2011 7/1/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  7/1/2011 DONE
Alarm Plan Check7/1/2011 7/1/2011 PASS
DetailsStephanie L. Cobbley
Approved with review comments.
PLANS TAKEN FRONT DESK ALARM  7/1/2011 DONE
Approved plans available at front counter.
Inspection Record Card- Fire7/1/2011 7/1/2011 DONE
DetailsPatricia Smith
Telephone call  7/1/2011 DONE
left vm for erin - permit ready and fees given
Permit Ready to Issue  7/1/2011 DONE