Permit Information
Permit NumberFIR11-00324
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 3300 S SHOSHONE ST
Project NameFAIRFIELD INN
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide monitoring for two new flow switches and two new backflow preventer tamper switches due to the sprinkler system being split from one riser into three risers. There are no written review comments. There is no associated building permit. See sprinkler permit FIR11-00308 for further information regarding the sprinkler work being done.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/13/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection9/6/20119/7/20119/7/2011APASS
DetailsForrest France
Corrections verified for completion. Fire alarm permit finaled.
INSP-Final Inspection8/31/20119/2/20119/2/2011AFAIL
DetailsForrest France
Final pending repair of three non-functional waterflow switches at the new riser manifold.
INSP-Alarm Testing8/15/20118/15/20118/16/2011PNR
DetailsForrest France
Issue and Print Permit  8/9/2011 DONE
Alarm Plan Check7/22/2011 7/22/2011 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  7/22/2011 DONE
Approved quick permit plans available at front counter.
Inspection Record Card- Fire7/22/2011 7/22/2011 DONE
DetailsTisha Gallop
Permit Ready to Issue  7/22/2011 DONE
DetailsTisha Gallop
Telephone call  7/22/2011 DONE
DetailsTisha Gallop
called Fire Sentry, left message with answering service that permit is ready.
Plan assigned to (Stephanie)7/8/2011 7/22/2011 DONE
DetailsStephanie L. Cobbley
Plan assigned to (Stephanie)7/8/2011 7/22/2011 DONE
DetailsStephanie L. Cobbley
Plan resubmittals received  7/20/2011 DONE
Telephone call  7/12/2011 DONE
Left a message for John Lopez regarding descrepencies in the scope of work.
1st review completed  7/12/2011 DONE
Alarm Plan Check7/12/2011 7/12/2011 FAIL
DetailsStephanie L. Cobbley
Resubmittal required. Show the backflow preventer tamper switch monitoring on the riser and calcs. If the flow switches are located in the stairwell of each floor, the monitor modules must be located with them and not all in the riser room as indicated. Ensure the application is signed and dated where shown (see page 3 of the application).
Miscellaneous action  7/12/2011 DONE
Faxed denied submittal to contractor
Telephone call  7/11/2011 DONE
Left a message for John Lopez regarding descrepencies in the scope of work.
Application received  7/8/2011