Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR11-00325
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 1301 N ORCHARD ST
Project NameCorrectional Industries
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide new modules to monitor a new sprinkler flow switch and two new backflow preventor tamper switches. The addressable devices will be tied in to the existing fire alarm system. There are no written review comments. Associated building permit: BLD11-00832 (CORRECTIONAL INDUSTRIES – CSC Building – entire 1st floor) Permit is to expand an existing 6,627 square foot 1st floor tenant into the entire 1st floor making them 17,910 square feet. This tenant will be vacating the 1,900 square feet they originally occupied on the 2nd floor under BLD07-03252. This building is fully fire sprinklered for area increase. Approval contingent upon adhering to the approved plans on file. Work to include: [installation / demolition of interior partition walls to create additional open office area, six additional offices, and two additional storage rooms], installation of new lighting, installation of new doors / accessible hardware, and finishes in compliance with chapter 8 of the 2009 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department.**TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/2/2011 DONE
Taken to records for scanning.
INSP-Final Inspection8/19/20118/22/20118/22/2011PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in8/16/20118/18/20118/18/2011AFAIL
DetailsForrest France
Riser supervision incorrectly reported as 2nd floor HVAC supervisory. Also noted an inoperable MP station and SD at the riser room.
Issue and Print Permit  7/18/2011 DONE
Plan assigned to (Stephanie)7/11/2011 7/12/2011 DONE
DetailsStephanie L. Cobbley
Plan assigned to (Stephanie)7/11/2011 7/12/2011 DONE
DetailsStephanie L. Cobbley
Telephone call  7/12/2011 DONE
Left a message for John Lopez regarding descrepencies in the scope of work.
1st review completed  7/12/2011 DONE
Alarm Plan Check7/12/2011 7/12/2011 PASS
DetailsStephanie L. Cobbley
The quick permit plans are approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  7/12/2011 DONE
Approved quick permit plans available at front counter.
Inspection Record Card- Fire7/12/2011 7/12/2011 DONE
DetailsPatricia Smith
Telephone call  7/12/2011 DONE
t/c w kelly - permit ready and fees given
Permit Ready to Issue  7/12/2011 DONE
Details
Telephone call  7/11/2011 DONE
Left a message for John Lopez regarding descrepencies in the scope of work.
Application received  7/11/2011