Permit Information
Permit NumberFIR11-00335
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 8013 W FAIRVIEW AVE
Project NameEmployment Solution - Shopko
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of adding and relocating sprinklers to accommodate new wall and ceiling configuration. The existing system is a 3”x2½”x1½” grid with 6” underground. The reference plans indicate that the original system was installed in 1986.


Building Department Scope:

Permit is to remodel an existing 4,852 square foot office space to be reduced to 2,209 square feet for this tenant. The left over 2,643 square feet is having restrooms stubbed in; however, it is not being reviewed for code compliance. This building is fully fire sprinklered for unlimited area. Approval is contingent upon adhering to the approved plans on file. Work to include: [installation / demolition of interior partition walls to create three offices, an orientation room, an open office area, and an accounting area, and enlarge the restrooms], installation of a new hi/low drinking fountain, installation of new light switching, installation of new accessible sales and service counter (if applicable), installation of new doors / accessible hardware, and finishes in compliance with chapter 8 of the 2009 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department.**TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/22/2011 DONE
DetailsTim Frost
Sent to Records for scanning.
INSP-Final Inspection7/26/20117/28/20117/28/2011APASS
DetailsTroy Cobbley
permit finaled
Miscellaneous action  7/26/2011 DONE
Received and approved as built hydraulic calculations. The calculations based on the revised sq ft has a safety factor of 33.9 Psi
INSP-Sprinkler Rough-in7/21/20117/21/20117/21/2011PPASS
DetailsTroy Cobbley
The sprinkler piping is ok to cover. But it appears several of the upright sprinklers are overspaced due to the new wall and an existing draft stop. Jim is going to provide verification that the new upright sprinkler spacing is adequate and will either remove the dry wall or add additional upright heads.
Plan assigned to (Tim)7/14/2011 7/20/2011 DONE
DetailsTim Frost
Sprinkler Plan Check7/20/2011 7/20/2011 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  7/20/2011 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  7/20/2011 DONE
DetailsTim Frost
Inspection Record Card- Fire7/20/2011 7/20/2011 DONE
DetailsPatricia Smith
Telephone call  7/20/2011 DONE
t/c w jim - permit ready and fees given
Permit Ready to Issue  7/20/2011 DONE
Details
Issue and Print Permit  7/20/2011 DONE
Application received  7/14/2011  
Case Summary  7/14/2011 DONE
DetailsTisha Gallop