Miscellaneous action | | | 12/16/2011 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 11/7/2011 | 11/8/2011 | 11/7/2011 | A | PASS |
Forrest France
|
|
|
Final walkthrough completed. Contractor to provide outside bell signage and repair one DP escutcheon as discussed. Permit finaled. Note: Inspection completed 11/7.
|
Fees Due Hold | 10/13/2011 | | 10/14/2011 | | DONE |
Darla L Downs
|
|
|
|
INSP-Final Inspection | 10/12/2011 | 10/13/2011 | 10/13/2011 | A | FAIL |
Troy Cobbley
|
|
|
The new flow switch has been installed but when testing it the outside alarm bell would barely ring and then quit. And then 10 to 20 seconds later would ring again and then quit. This was an issue years ago with Ames backflow preventors but this one is a Wilkins. It finally activated the fire alarm panel but this issue needs addressed so that the bell continues to ring when the flow switch is activated.
|
INSP-Final Inspection | 10/6/2011 | 10/6/2011 | 10/6/2011 | P | PART |
Forrest France
|
|
|
Final walkthrough completed, minor adjustments done while on site. Verified added head at the dry valve room. Fire alarm interconnections tested. Final pending repair of non-functional waterflow switch at the main riser.
|
INSP-Sprinkler Rough-in/Hydro | 10/5/2011 | 10/6/2011 | 10/6/2011 | A | PASS |
Forrest France
|
|
|
OH hydrostatic re-test passed.
|
INSP-Sprinkler Rough-in | 10/4/2011 | 10/5/2011 | 10/5/2011 | A | FAIL |
Forrest France
|
|
|
Hydrostatic test of the overhead system failed due to a 10 psi. pressure loss at the guage. Relocated heads at the 1st floor corridor and 2nd floor utility rooms okayed.
|
INSP-Sprinkler Rough-in | 9/28/2011 | 9/30/2011 | 9/30/2011 | A | FAIL |
Forrest France
|
|
|
Upright heads at the first floor corridor are blocked by adjacent truss webs due to distance of the deflector from the deck, two pendent heads at classroom 201 need to meet fig. 8.6.5.1.2(b) NFPA 13, storage room 204 uprights are obstructed by ductwork. Remainder of drop ceiling areas are okay for cover.
|
INSP-Sprinkler Rough-in | 9/23/2011 | 9/23/2011 | 9/23/2011 | P | PART |
Forrest France
|
|
|
See plans for annotations regarding areas inspected to date.
|
INSP-Sprinkler Rough-in | 9/20/2011 | 9/20/2011 | 9/20/2011 | P | PART |
Forrest France
|
|
|
Reinspection for the second floor classrooms and 1st floor RR completed. Okay for cover at rooms 203, 205 and 206 new addition- noted one missing seismic brace at room 203. Restrooms 1st floor east side also approved for cover.
|
INSP-Sprinkler Rough-in | 9/16/2011 | 9/16/2011 | 9/16/2011 | P | FAIL |
Forrest France
|
|
|
Inspection for cover at the three 2nd floor classrooms and both the 1st floor restrooms failed due to obstructed heads, one missing head, missing seismic bracing, sprig in need of adjustment, access, etc.
|
INSP-Sprinkler Rough-in/Hydro | 9/6/2011 | 9/6/2011 | 9/6/2011 | A | PART |
Forrest France
|
|
|
See approved plans for marked and dated locations inspected to date.
|
INSP-Sprinkler Rough-in | 8/30/2011 | 8/30/2011 | 8/31/2011 | A | PART |
Forrest France
|
|
|
Reference stamped plan set for locations inspected today including the 1st floor restrooms east side, under stairway heads, and the 2nd floor classroom remodel.
|
INSP-Sprinkler Rough-in | 8/25/2011 | 8/25/2011 | 8/25/2011 | P | PART |
Forrest France
|
|
|
Verified corrections at the administration area and kindergarden classroom, okay to sheetrock the deck only at classrooms 113 and 115. Discussed possible obstruction issues at the soffit in rooms 113 and 115.
|
INSP-Sprinkler Rough-in/Hydro | 8/10/2011 | 8/12/2011 | 8/12/2011 | A | PART |
Forrest France
|
|
|
Inspection completed for portions of the 1st and 2nd floors remodeled and new additions as marked on stamped plan set. Noted items include; 1st floor- missing 4 seismic braces, overspaced uprights at room 101 and 109, 2nd floor- pipe sizing at room 200 does not match plan, need to sheetrock concealed space or provide sprinkler protection, provide clearance at the floor for the 2" dry feed to the wheelchair ramp. Okay to cover new exterior canopy and ceiling above the ramp.
|
Plan assigned to (Tim) | 7/20/2011 | | 7/29/2011 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 7/29/2011 | | 7/29/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/29/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 7/29/2011 | | 7/29/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 7/29/2011 | | DONE |
|
|
|
t/c w jim - permit ready and fees given
|
Permit Ready to Issue | | | 7/29/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/29/2011 | | DONE |
|
|
|
|
Miscellaneous action | | | 7/26/2011 | | DONE |
Tisha Gallop
|
|
|
picked up denied plans
|
Plan resubmittals received | | | 7/26/2011 | | DONE |
Tisha Gallop
|
|
|
received three copies of application, submittal docs and plans; routed to Fire Review.
|
Sprinkler Plan Check | 7/25/2011 | | 7/25/2011 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 7/25/2011 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 7/25/2011 | | DONE |
|
|
|
Emailed contractor review.
|
Telephone call | | | 7/25/2011 | | DONE |
|
|
|
t/c w jim - permit denied - needs to be picked up and resubmitted
|
Application received | | | 7/20/2011 | | |
|
|
|
|