Permit Information
Permit NumberFIR11-00362
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 8049 W FAIRVIEW AVE
Project NameSHOPKO PLAZA
Customer Number 
ePlanReviewNo
Description
(CITY BUFFET ASIAN RESTAURANT)Install small kitchen hood system for serving area of restaurant. Hood system has 3 nozzels and is seperate from the large hood system in the food prep area of the kitchen. This small system includes shut off for the gas and fan as well as a manual pull station and heat sensitive solder links fro auto trip sevice.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/19/20119/19/20119/19/2011PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection9/12/20119/13/20119/13/2011PFAIL
DetailsTroy Cobbley
The hood suppression system operated correctly. But all of the correct sign off paper work had not been provided and the appliance layout for the large hood did not match the paper work.
INSP-Final Inspection9/8/20119/9/20119/9/2011ANR
DetailsForrest France
Not ready for final inspection per conversation with contractor. Discussed requirements for acceptance testing per IFC.
Application received  7/21/2011  
Permit Ready to Issue  7/21/2011 DONE
DetailsChristina Prado
Issue and Print Permit  7/21/2011 DONE