Miscellaneous action | | | 9/22/2011 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 8/11/2011 | 8/12/2011 | 8/12/2011 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 8/10/2011 | 8/11/2011 | 8/11/2011 | A | FAIL |
Troy Cobbley
|
|
|
There is a draft stop, leftover wall top, that is blocking upright sprinkler coverage. This obstruction was not shown on the plans. The upright coverage off of the wall is around 163 sq. ft. Per the hydraulic calculations and the existing upright sprinkler spacing 120 sq. ft. is the max.
|
Plan assigned to (Tim) | 7/29/2011 | | 8/10/2011 | | DONE |
Tim Frost
|
|
|
|
Plan resubmittals received | | | 8/10/2011 | | |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 8/10/2011 | | 8/10/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/10/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 8/10/2011 | | 8/10/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 8/10/2011 | | DONE |
|
|
|
t/c w brodie - permit ready and fees given
|
Permit Ready to Issue | | | 8/10/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/10/2011 | | DONE |
Barbara Stitt
|
|
|
|
Sprinkler Plan Check | 8/4/2011 | | 8/4/2011 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 8/4/2011 | | DONE |
Tim Frost
|
|
|
|
Telephone call | | | 8/4/2011 | | DONE |
|
|
|
t/c w brodie - permit denied - needs to be picked up and resubmitted
|
Application received | | | 7/29/2011 | | |
|
|
|
|