Miscellaneous action | | | 11/14/2011 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 10/19/2011 | 10/20/2011 | 10/20/2011 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 10/18/2011 | 10/19/2011 | 10/19/2011 | P | FAIL |
Troy Cobbley
|
|
|
The technician did not have a "butset" to verify the phone numbers that have been set up for the new facp. No inspection was performed.
|
INSP-Final Inspection | 10/17/2011 | 10/18/2011 | 10/18/2011 | P | CANC |
Troy Cobbley
|
|
|
Troy, Please let me know an approximate time, so I can let everyone know. Jason ###-#### Phone #: ###-#### >> Inspection requested via web by Jason Minnick Inspection cancelled from web by: Jason Minnick
|
Fees Due Hold | 10/13/2011 | | 10/14/2011 | | DONE |
|
|
|
|
Issue permit | | | 10/14/2011 | | DONE |
|
|
|
Payment received via Govolutions
|
Plan assigned to (Stephanie) | 9/30/2011 | | 10/10/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 10/10/2011 | | 10/10/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 10/10/2011 | | DONE |
|
|
|
Approved redlined plan modification documents available at front counter.
|
Inspection Record Card- Fire | 10/10/2011 | | 10/10/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 10/10/2011 | | DONE |
|
|
|
t/c w lisa - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 10/10/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/10/2011 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/30/2011 | | DONE |
Tisha Gallop
|
|
|
PLAN MODIFICATION: received two copies of application, submittal folder and plans; routed to fire review.
|
INSP-Final Inspection | 9/22/2011 | 9/23/2011 | 9/23/2011 | A | FAIL |
Troy Cobbley
|
|
|
A model 5230 remote annunciator has been installed on the face of the panel so that alarm functions are provided per IFC 906. After starting the testing it was found that the manual pull station when put in the normal "off alarm" condition the panel would self restore which is not allowed. Per NFPA 72 - 23.8.2.9 the panel can only be reset at the panel itself, not at this initiating device. Also in the course of researching this I was notified by the fire alarm panel manufacture that this panel is not listed for stand alone applications but is listed as a dialer. A panel needs to be installed that meets the intended application and this shall be submitted to the city for review as a plan modification.
|
INSP-Final Inspection | 9/22/2011 | 9/22/2011 | 9/22/2011 | P | CANC |
Troy Cobbley
|
|
|
Was not able to test the fire alarm since the fire sprinkler contractor had not been scheduled to test the dry system
|
INSP-Final Inspection | 9/20/2011 | 9/20/2011 | 9/20/2011 | P | CANC |
Troy Cobbley
|
|
|
Jason Phone #: ###-####
|
INSP-Final Inspection | 9/19/2011 | 9/20/2011 | 9/20/2011 | A | FAIL |
Troy Cobbley
|
|
|
There is no audible or visual annunciation of an alarm condition at the fire alarm panel as required by IFC 906. Burl is going to install a remote annunciator at the panel and re-inspect for this afternoon.
|
Issue and Print Permit | | | 8/12/2011 | | |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 8/1/2011 | | 8/4/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 8/4/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 8/4/2011 | | 8/4/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 8/4/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Override - Parcel Holds | | | 8/4/2011 | | |
|
|
|
|
Inspection Record Card- Fire | 8/4/2011 | | 8/4/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 8/4/2011 | | DONE |
|
|
|
t/c w lisa - permit ready and fees given
|
Override - Parcel Holds | | | 8/4/2011 | | |
|
|
|
|
Permit Ready to Issue | | | 8/4/2011 | | DONE |
|
|
|
|
Application received | | | 8/1/2011 | | |
|
|
|
|