Permit Information
Permit NumberFIR11-00378
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 440 N CLOVERDALE RD
Project NameACHD TIRE SHOP EXPANSION
Customer Number 
ePlanReviewNo
Description
10-10-11 PLAN MODIFICATION (no additional initiating devices affected): This plan modification is to change the fire alarm pane from a Silent Knight 5104B to a Silent Knight 5208. In addition, the previous submittal indicated monitoring for a wet sprinkler system, however it is actually a dry system, therefore the quantity and type of devices being monitored has been revised.

8-4-11:This fire alarm permit is to provide a new fire alarm panel for sprinkler system monitoring. Included in this permit scope of work is a pull station, a voluntary smoke detector above the FACP, monitoring the sprinkler system valves, and voluntarily monitoring the Knox box.

Associated building permit: BLD10-02865 Ada County Highway District Tire Shop Expansion - To demolish and remove two small sheds and construct a 1,545 square foot, one story, masonry wall and wood framed tire shop expansion and related site improvements. The expansion will be located on the west side of an existing 1,535 sq. ft., one story shop building. The expansion will include a 1,030 square foot, tire storage area, a 185 square foot break room with an attic access floor above and a 330 square foot, tank storage room. This permit also includes updating the lighting at the existing shop building. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  11/14/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection10/19/201110/20/201110/20/2011APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/18/201110/19/201110/19/2011PFAIL
DetailsTroy Cobbley
The technician did not have a "butset" to verify the phone numbers that have been set up for the new facp. No inspection was performed.
INSP-Final Inspection10/17/201110/18/201110/18/2011PCANC
DetailsTroy Cobbley
Troy, Please let me know an approximate time, so I can let everyone know. Jason ###-#### Phone #: ###-#### >> Inspection requested via web by Jason Minnick Inspection cancelled from web by: Jason Minnick
Fees Due Hold10/13/2011 10/14/2011 DONE
Details
Issue permit  10/14/2011 DONE
Payment received via Govolutions
Plan assigned to (Stephanie)9/30/2011 10/10/2011 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check10/10/2011 10/10/2011 PASS
DetailsStephanie L. Cobbley
Plan modification approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  10/10/2011 DONE
Approved redlined plan modification documents available at front counter.
Inspection Record Card- Fire10/10/2011 10/10/2011 DONE
DetailsPatricia Smith
Telephone call  10/10/2011 DONE
t/c w lisa - permit (plan mod) ready and fees given
Permit Ready to Issue  10/10/2011 DONE
Details
Issue and Print Permit  10/10/2011 DONE
Plan resubmittals received  9/30/2011 DONE
DetailsTisha Gallop
PLAN MODIFICATION: received two copies of application, submittal folder and plans; routed to fire review.
INSP-Final Inspection9/22/20119/23/20119/23/2011AFAIL
DetailsTroy Cobbley
A model 5230 remote annunciator has been installed on the face of the panel so that alarm functions are provided per IFC 906. After starting the testing it was found that the manual pull station when put in the normal "off alarm" condition the panel would self restore which is not allowed. Per NFPA 72 - 23.8.2.9 the panel can only be reset at the panel itself, not at this initiating device. Also in the course of researching this I was notified by the fire alarm panel manufacture that this panel is not listed for stand alone applications but is listed as a dialer. A panel needs to be installed that meets the intended application and this shall be submitted to the city for review as a plan modification.
INSP-Final Inspection9/22/20119/22/20119/22/2011PCANC
DetailsTroy Cobbley
Was not able to test the fire alarm since the fire sprinkler contractor had not been scheduled to test the dry system
INSP-Final Inspection9/20/20119/20/20119/20/2011PCANC
DetailsTroy Cobbley
Jason Phone #: ###-####
INSP-Final Inspection9/19/20119/20/20119/20/2011AFAIL
DetailsTroy Cobbley
There is no audible or visual annunciation of an alarm condition at the fire alarm panel as required by IFC 906. Burl is going to install a remote annunciator at the panel and re-inspect for this afternoon.
Issue and Print Permit  8/12/2011  
DetailsBarbara Stitt
Plan assigned to (Stephanie)8/1/2011 8/4/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  8/4/2011 DONE
Alarm Plan Check8/4/2011 8/4/2011 PASS
DetailsStephanie L. Cobbley
Approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  8/4/2011 DONE
Approved redlined plans available at front counter.
Override - Parcel Holds  8/4/2011  
Inspection Record Card- Fire8/4/2011 8/4/2011 DONE
DetailsPatricia Smith
Telephone call  8/4/2011 DONE
t/c w lisa - permit ready and fees given
Override - Parcel Holds  8/4/2011  
Permit Ready to Issue  8/4/2011 DONE
Details
Application received  8/1/2011