Miscellaneous action | | | 2/24/2012 | | DONE |
|
|
|
plans taken to records for scanning
|
INSP-Final Inspection | 1/25/2012 | 1/26/2012 | 1/26/2012 | A | PASS |
Forrest France
|
|
|
Verified noted corrections, inspection passed. Permit finaled.
|
INSP-Final Inspection | 1/9/2012 | 1/10/2012 | 1/10/2012 | A | FAIL |
Troy Cobbley
|
|
|
Provide for location and testing of EOL voltage drops. The new manual pull station located in the waiting room is located too far from the door and placed too low. See IFC 907.5.2. The duct smoke detectors tested ok.
|
Plan assigned to (Stephanie) | 8/1/2011 | | 8/16/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 8/16/2011 | | 8/16/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 8/16/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Inspection Record Card- Fire | 8/16/2011 | | 8/16/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 8/16/2011 | | DONE |
|
|
|
t/c w dante - permit ready and fees given
|
Permit Ready to Issue | | | 8/16/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/16/2011 | | DONE |
|
|
|
|
Telephone call | | | 8/15/2011 | | DONE |
|
|
|
Received a call from John H. At CH2MHill and was given the information requested.
|
1st review completed | | | 8/12/2011 | | DONE |
|
|
|
|
Telephone call | | | 8/12/2011 | | DONE |
|
|
|
Spoke to Charlie at Simplexgrinnell regarding questions about the location of the new pull station and why they are putting duct detectors on both the supply and return of the RTU. He said he would have to get back to me on Monday.
|
Application received | | | 8/1/2011 | | |
|
|
|
|