Miscellaneous action | | | 10/13/2011 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 9/28/2011 | 9/29/2011 | 9/29/2011 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 9/7/2011 | 9/8/2011 | 9/8/2011 | A | FAIL |
Troy Cobbley
|
|
|
The induct detectors and dampers operated correctly and reported to the fire alarm panel as alarm at zone 14. The problem is per the monitoring company no signals have been received on this account since september of 2010. I let Tom Gainer with Boise Fire about the situation.
|
Plan assigned to (Stephanie) | 8/4/2011 | | 8/8/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan assigned to (Stephanie) | 8/4/2011 | | 8/8/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 8/8/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 8/8/2011 | | 8/8/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit approved - no written review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 8/8/2011 | | DONE |
|
|
|
Approved quick permit plans available at front counter.
|
Inspection Record Card- Fire | 8/8/2011 | | 8/8/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 8/8/2011 | | DONE |
|
|
|
t/c w phil - permit ready and fees given
|
Permit Ready to Issue | | | 8/8/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/8/2011 | | |
|
|
|
|
Application received | | | 8/4/2011 | | |
|
|
|
|