Permit Information
Permit NumberFIR11-00394
StatusFinaled
Name PEAK ALARM
Site Address 1125 W AMITY RD
Project NameNORCO OFFICE BUILDING
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to replace the existing fire alarm system with new and bring the building fire alarm system up to meet current code requirements (2009 IFC and 2010 NFPA 72). The system shall include a full manual system, notification throughout the office spaces (the warehouse does not require notification since it has rated separation from the office areas), sprinkler system monitoring, and elevator recall/shunt trip functions. No HVAC has been indicated on the plans. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  3/9/2016 DONE
Case Summary  12/9/2015 DONE
INSP-Final Inspection9/3/20159/4/20159/4/2015APASS
DetailsJim Page
Final fire alarm inspection passed/complete
FIR-Aging Inspection8/24/20158/24/20158/31/2015 PEND
DetailsTroy Cobbley
Project is currently being inspected
INSP-Final Inspection8/26/20158/28/20158/28/2015PFAIL
DetailsJim Page
Tested all devices with fire system, elevator shunt, elevator recall as well as sprinkler system, devices reported to panel and central station. Performed audible/visual test, strobes and audibles are not sync up, some audibles are temporal, others are solid, needs to be repaired/replaced before next inspection.
FIR-Aging Inspection4/1/20144/1/20144/2/2014 DONE
DetailsForrest France
Need site inspection request.
FIR-Aging Inspection11/21/201311/21/201311/21/2013 DEFR
DetailsForrest France
FIR-Aging Inspection6/19/20136/19/20136/19/2013 DONE
DetailsForrest France
FIR-Aging Inspection3/20/20133/20/20133/21/2013 DONE
DetailsForrest France
FIR-Aging Inspection12/7/201212/7/201212/7/2012 PEND
DetailsForrest France
FIR-Aging Inspection9/7/20129/7/20129/13/2012 PEND
DetailsForrest France
FIR-Aging Inspection5/1/20125/1/20125/1/2012 DONE
DetailsForrest France
In progress
Fees Due Hold10/13/2011 10/25/2011 DONE
DetailsPatricia Smith
Issue and Print Permit  9/12/2011 DONE
Plan assigned to (Stephanie)8/8/2011 8/29/2011 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check8/29/2011 8/29/2011 PASS
DetailsStephanie L. Cobbley
Plans approved with review comments.
PLANS TAKEN FRONT DESK ALARM  8/29/2011 DONE
Approved plans available at front counter.
Inspection Record Card- Fire8/29/2011 8/29/2011 DONE
DetailsPatricia Smith
Telephone call  8/29/2011 DONE
t/c w mike - permit ready and fees given
Permit Ready to Issue  8/29/2011 DONE
Details
1st review completed  8/22/2011 DONE
Alarm Plan Check8/22/2011 8/22/2011 FAIL
DetailsStephanie L. Cobbley
Plans denied - see review comments and redlined plans.
Miscellaneous action  8/22/2011 DONE
Faxed review comments to installing contractor.
Miscellaneous action  8/22/2011 DONE
Denied plans taken to front counter for contractor to pick up.
Plan resubmittals received  8/22/2011 DONE
DetailsTisha Gallop
received application, and two copies of submittal folder and plans; routed to Fire Review.
Application received  8/8/2011