Miscellaneous action | | | 12/16/2011 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 11/17/2011 | 11/18/2011 | 11/18/2011 | A | PASS |
Forrest France
|
|
|
Correction items field verified, outside bell tested okay. Note: light fixtures at some locations are not installed- be aware of possible obstruction issues that may develop due to fixture type and size.
|
INSP-Final Inspection | 11/15/2011 | 11/16/2011 | 11/16/2011 | A | FAIL |
Forrest France
|
|
|
Missing backflow certification, control valves need locked or sealed in the open position, riser is not secured to the structure, inspectors test and drain does not terminate outside, noted leaking feed main in the crawlspace.
|
INSP-Final Inspection | 11/14/2011 | 11/15/2011 | 11/15/2011 | A | DEFR |
Forrest France
|
|
|
Don Phone #: ###-####
|
INSP-Sprinkler Rough-in | 9/8/2011 | 9/8/2011 | 9/8/2011 | P | PART |
Forrest France
|
|
|
Inspection for cold cavity protection completed acceptable. Overhead install approved for cover.
|
INSP-Sprinkler Rough-in | 9/7/2011 | 9/7/2011 | 9/7/2011 | P | NR |
Forrest France
|
|
|
Don Phone #: ###-####
|
INSP-Sprinkler Rough-in | 8/31/2011 | 9/1/2011 | 9/1/2011 | A | PART |
Forrest France
|
|
|
Overhead rough-in okayed. Approval for cover pending cold cavity protection verification.
|
Plan assigned to (Tim) | 8/30/2011 | | 8/31/2011 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 8/31/2011 | | 8/31/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 8/31/2011 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/31/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 8/31/2011 | | 8/31/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 8/31/2011 | | DONE |
|
|
|
t/c w don - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 8/31/2011 | | DONE |
|
|
|
|
(F) Reprint permit | | | 8/31/2011 | | DONE |
Barbara Stitt
|
|
|
|
CHANGE STATUS TO (ISS) | | | 8/31/2011 | | DONE |
Barbara Stitt
|
|
|
|
Plan resubmittals received | | | 8/30/2011 | | DONE |
Tisha Gallop
|
|
|
Plan Modification: Received three copies of applicaiton, submittal documents and plans; routed to Fire Review.
|
Issue and Print Permit | | | 8/24/2011 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 8/10/2011 | | 8/22/2011 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 8/22/2011 | | 8/22/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/22/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 8/22/2011 | | 8/22/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 8/22/2011 | | DONE |
|
|
|
t/c w don - permit ready and fees given
|
Permit Ready to Issue | | | 8/22/2011 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/17/2011 | | DONE |
Tisha Gallop
|
|
|
received three copies of application, submittal small documents and plans; routed to fire review.
|
Sprinkler Plan Check | 8/11/2011 | | 8/11/2011 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 8/11/2011 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 8/11/2011 | | DONE |
|
|
|
Emailed contractor review.
|
Telephone call | | | 8/11/2011 | | DONE |
|
|
|
t/c w don - permit denied - needs to be picked up and resubmitted
|
Application received | | | 8/10/2011 | | |
|
|
|
|