Permit Information
Permit NumberFIR11-00398
StatusFinaled
Name CRANE ALARM COMPANY
Site Address 8645 W FRANKLIN RD
Project NameA.T. SOLUTIONS BATHROOM
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide notification in the new restroom and notification in the corridor/hallway created by the new restroom walls. See redlines on the drawings. There are no written review comments. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. Associated building permit: BLD11-01132 A.T. SOLUTIONS BATHROOM- Permit for minor tenant improvements to an existing 13,550 sq. ft tenant space with work to include the construction of a new ADA compliant restroom. The existing light fixtures will be repositioned and no additional fixtures will be installed. This space does not require additional restroom fixtures per the occupant load but are being added for the convenience of the occupants. CDM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/2/2011 DONE
Taken to records for scanning.
INSP-Final Inspection8/10/20118/11/20118/11/2011APASS
DetailsTroy Cobbley
Permit finaled
Application received  8/10/2011  
Plan assigned to (Stephanie)8/10/2011 8/10/2011 DONE
DetailsStephanie L. Cobbley
Plan assigned to (Stephanie)8/10/2011 8/10/2011 DONE
DetailsStephanie L. Cobbley
Plan resubmittals received  8/10/2011 DONE
DetailsTisha Gallop
received additional info requested
Telephone call  8/10/2011 DONE
Called Tim with Crane Alarm to request new data sheets, battery calculations, and voltage drops due to documentation not being legible. In addition, there were new walls created due to the new restroom however the only notification shown is the new device in the restroom. Requested a new floorplan indicating existing notification so spacing could be verified.
Miscellaneous action  8/10/2011 DONE
Requested information received.
1st review completed  8/10/2011 DONE
Alarm Plan Check8/10/2011 8/10/2011 PASS
DetailsStephanie L. Cobbley
Quick permit plans approved - see redlined drawings - no written review comments.
PLANS TAKEN FRONT DESK ALARM  8/10/2011 DONE
Approved, redlined quick permit plans available at front counter.
Inspection Record Card- Fire8/10/2011 8/10/2011 DONE
DetailsPatricia Smith
Telephone call  8/10/2011 DONE
t/c w tim - permit ready and fees given
Permit Ready to Issue  8/10/2011 DONE
Details
Issue and Print Permit  8/10/2011 DONE